Single zone AOV User Manual
PRODUCT OVERVIEW
11
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Technical Specification
General Specification
Enclosure
Steel IP30. Epoxy powder coated Interpon Radon, silver
grey
Temperature range:
-5°C to +40°C
Maximum Relative Humidity:
95%
Number of conventional/twin wire
detection circuits
1
Conventional/twin wire detector
compatibility
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
Cabling
Fire resistant screened cable, minimum size 1mm
2
. Max
cable length 1Km (20 Ohm). Fire Burn, FP200 or
equivalent (max capacitance 1uF, max inductance 1
millihenry).
Suitable cable glands must be used
Terminal capacity
0.5mm
2
to 2.5mm
2
solid or stranded wire.