Single zone AOV User Manual
SETUP AND PROGRAMMING
31
Approved Document Ref: UI-SZAOV-01 Issue 2.01
With the Vent Closed LED pulsing, the other LEDs listed above will show the currently set time
(factory default = 60 seconds). Use buttons 1 & 3 to increase or decrease the time by 5 seconds
at a time. A minimum time of 10 seconds and a maximum time of 300 seconds can be set.
Press the ENTER button to set the time and return to the main menu.
OPTION 3 (Vent Open LED and Vent Closed LED) Disable Actuator Short Circuit Monitoring
Use this option to inhibit the monitoring of the short circuit condition on the actuator output. This
allows actuators that present a resistance of less than
10Ω to be used. However, disabling the
short circuit monitoring might not meet the requirements of local regulations. Connecting a
resistance of less that 1Ω might cause damage to the actuator drive circuit.
With the Vent Open LED and the Vent Closed LED pulsing, the current status is represented by
the Rain Status LED:
•
LED OFF = Normal, actuator short circuit is monitored.
•
LED ON = Actuator short circuit is not monitored
Use button 2 to change the status. Press the ENTER button to save the setting and return to
the main menu.
OPTION 4 (Input LED) Disable Battery Monitoring
Use this option to disable the battery monitoring (i.e., batteries not installed).
With the Input LED pulsing, the current status is represented by the Power Supply Fault LED:
•
LED OFF = Normal, batteries are monitored
•
LED ON = Battery monitoring disabled.
Use button 2 to change the status. Press the ENTER button to save the setting and return to the
main menu.
OPTION 5 (Detector LED) Disable Muted Tone Beeps
Use this option to inhibit the intermittent beep that still occurs when a fault or fire tone has been
muted using the Mute Buzzer button.
With the Detector LED pulsing, the current status is represented by the PIR Status LED:
•
LED OFF = Normal, panel beeps intermittently when the panel buzzer has been muted
•
LED ON = Muted beeps disabled.
Use button 2 to change the status. Press the ENTER button to save the setting and return to the
main menu.
Содержание SZAOV