Single zone AOV User Manual
PRODUCT OVERVIEW
18
Approved Document Ref: UI-SZAOV-01 Issue 2.01
AUX (+ -)
A maintained magnetic vent 28v output for external magnetically controlled devices.
Switches off to release magnet in the alarm condition. The output can be inverted using DIL
switch 2
‘AUX INVERT’ on the main PCB.
May also be used as an alternative vent auto close output.
FIRE (NO NC COM)
Common alarm changeover relay contacts, max 3A at 30VDC (unfused). Activates when an
alarm condition exists on the open/close input or detector circuit.
FAULT (NC NO COM)
Common fault signal changeover relay contacts, max 3A at 30VDC (unfused). Normally
energised (failsafe) contacts change-over when any fault is active on the panel or in the
event of total power loss.
SENSOR (+ -)
Connections for battery temperature sensor.
BATTERY (+ -)
Output connections for 7Ah 12Volt batteries charging (temperature compensated). 27.3VDC
output at 20C, Max. charging current: 700mA.