DCX
34 Block 6
Configuration of
8 special calculation
6.3.5. Math Function (Block 6)
Block
Channel 1...8
Number
Range:
0…8
0:
Math function channel x OFF (Standard)
At the output of channel x of this block "0" is always present
1:
Sum function (a+b+c)
More parameter values 2 to 8 are described in the Reference
Manual
4 6 x 0 i
Function selection
OFF / ON
Level
Range:
01…58
Standard: 51
1. Digit: block
2. Digit: channel
First signal source (a) for the Math function x
4 6 x I I
1. Signal source (a)
Range:
01…58
Standard: 52
1. Digit: block
2. Digit: channel
Second signal source (b) for the Math function x
4 6 x 2 I
2. Signal source (b)
The input values of the signal sources can be scaled separately. When scaling the result must still be
within the permitted range. The result will be limited to ± 200% . A Tabular overview of signal sources is
given in chapter 8
(Block 6)
Math function [1...8]
46x00
F(a,b,c)
Selection number: 6x
01..58
46x31
c
36x31
36x32
c
01..58
46x21
b
36x21
36x22
b
01..58
46x11
a
Example 1
Example 3
Example 2
(Standard)
Source 1
Example 4
36x11
Scaling at
0-signal (0%)
36x12
Scaling at nominal
signal (100%)
a