11
Expert Sensor Box 7211/7212
Configuration
Configuration - HTTP
2.2.3
HTTP port: Here can be set the port number of the internal HTTP. Possible values ?
?
are from 1 to 65534
(default: 80). If you do not use the default port, you must append the port number to the address with a
colon to address the device from a web browser. Such as: "http://192.168.0.2:800"
Enable auto refresh HTML: If this is activated, the information of the status page is automatically upda-
ted via http request (AJAX).
Require HTTP password: If desired, a http password protection can be enabled. In this case, an admin
password and a user password can be assigned. The password can have up to 15 characters. User
can log in by entering the user's password to query the status information and make changes to ports
(if applicable). Admins have the privileges of a User and can change the Configuration settings. In the
username field of the password input mask the names "admin" and "user" are supported. In the factory
defaults the password for the admin is set to "admin" resp. "user" for the user password.
If you have forgotten your password, please activate the bootloader mode and then turn off
the password prompt in GBL_Conf.exe.