6
Expert Sensor Box 7211/7212
Device Description
or
·
Remove the power supply
·
Hold down the button (or the "Select" button for devices with 2 buttons). If the push button is reces-
sed, use a pin or paper clip
·
Connect the operating voltage
by Software: (only if "Enable FW to BL" was previously activated in GBL_Conf.exe)
·
Start GBL_Conf.exe
·
Do a network search with the "Search" menu action
·
Activate in menu "Program Device" the item "Enter Bootloader"
Whether the device is in bootloader mode, is indicated by the flashing of the status LED, or it is shown
in GBL_Conf.exe, after a renewed device search, with the appendix "BOOT-LDR" after the device na-
me. In bootloader mode the program GBL_Conf.exe can disable the password and the IP ACL, perform
a firmware update, and restore the factory settings.
Activation of the bootloader mode and an abandonment of the bootloader does not change
the state of the power or output ports as long as the supply voltage is maintained.
Abandonment of the Bootloader Mode
via push button:
·
Hold both buttons for 3 seconds (only if the device has 2 buttons)
or
·
Remove and connect the power supply without operating a button
by Software:
·
Start GBL_Conf.exe
·
Do a network search with the "Search" menu action
·
In menu "Program Device" activate the item "Enter Firmware"
Factory Reset
If the device is in bootloader mode, it can always be put back to its factory default. All TCP / IP settings
are reset in this operation.
via push button:
·
Activate the Bootloader Mode of the device
·
Hold down the button (or the "Select" button for devices with 2 buttons) for 6 seconds. If the push
button is recessed, use a pin or paper clip
·
The status LED will blink in a fast rhythm, please wait until the LED blinks slowly (about 5 seconds)
by Software:
·
Activate the Bootloader Mode of the device
·
Start GBL_Conf.exe
·
In menu "Program Device" activate the item "Reset to Fab Settings"
·
The status LED will blink in a fast rhythm, please wait until the LED blinks slowly (about 5 seconds)