Guardian MIZCS Скачать руководство пользователя страница 13

Guardian Telecom Inc. 

Installation Programming Operation 

Merge/Isolate Zone Control System 

 

Page 13 

 

 

 

Installation of MICABs and MICONs 

 

Installing the Merge/Isolate Master Switch Unit (MICAB) 

 

WARNING – high voltages are present in this equipment when it is 
connected to the power source. 

 

  Follow all appropriate electrical codes and use only approved electrical 

fittings for the installation. 

 

  Install the MICAB in the rack. 

  If the Control System is being installed in a five channel system determine 

which channel will be dedicated to the Merge/Isolate function. 

See: Figure 2 - 
Dimensions MICON & 
MICAB 

  Ensure that none of the electrical connection circuits are live. 

  Following the color codes in the System Wiring Connections table connect 

the Page Lines and the dedicated Talk Lines from each zone to the zone 
connectors on the back panel of the MICAB. 

  Following the wire identification information in the MICAB to MICON Wiring 

Connections table connect the MICON(s) to the MICAB.  Up to six MICONs 
can be connected to the MICAB. 

See: Figure 11 - 
Page/Talk System 
Wiring (typical 
application) 

 

See: MICAB Back Panel 
Connector Tables
 and 
Installing Multiple 
Merge/Isolate Controllers 
(MICONs) 

  Connect the Alarm Generator. 

See: AG17 Manual 

  To reduce noise on the Page/Talk system, 33 Ohm resistors – usually 

installed in a Line Balance Unit (LBU) – are connected across every page 
& talk line in every zone in/near the MICAB.  The MICON provides the 
loading for all the page and dedicated merge talk lines. Resistors for the 
un-merged talk lines should be placed near the MICAB and remote LBU’s 
must not be connected. 

See: LBU Manual 

  If a Telephone interface is to be connected into the system do so at this 

time. 

See: PTTI Manual 

  Jumpers JP1, JP2, JP3, JP4 and JP5 are configured at the factory for the 

most common setup.  If changes to the system occur relocate jumpers to 
the appropriate positions. 

See: Figure 9 - MICAB 
Jumper Settings 

  Ensure all connections are secure. 

 

  Connect the power supply to J1.  The voltage is set at the factory to 

120 VAC, 230 VAC or 24 VDC.  Ensure that the power being supplied is 
correct by checking the label on the back of the MICAB. Connect the 
MICAB power cord to the proper power source then turn on the power 
switch. 

  Program the system. 

  Adjust the front and back panel potentiometers. 

 

 

See: Programming of 
MICABs and MICONs 

See: Potentiometer 
Adjustments on the 
MICABs 

  Test the system as described in the operation section. 

See: Operation 

Содержание MIZCS

Страница 1: ...Merge Isolate Zone Control System Model MIZCS Installation Programming Operation P006737 Rev C 151116 11 16 2015 11 32 AM Ph 403 258 3100 email info guardiantelecom com www guardiantelecom com ...

Страница 2: ... Replacement Parts 27 Warranty 28 Disclaimer 28 Warning 28 Service Telephone Number 28 Feedback 28 Guardian Product Return 29 Page Talk System Models and Options 30 Typical Page Talk Installation 31 Table of Figures Figure 1 System Block Diagram 6 Figure 2 Dimensions MICON MICAB 6 Figure 3 MICON Features 7 Figure 4 MICON Desk Top Mounting 7 Figure 5 MICON Wall Mounting 7 Figure 6 Back Panel Wiring...

Страница 3: ...two summary alarms in the form of LED indicators The inputs for these are located on the MICAB and are a simple dry contact format Some examples for use of the two alarms monitors are the facility alarm activation which could show that an alarm has been activated somewhere in the facility either from the MICON or from an external switch The other could be tied into a UPS or door switch or other se...

Страница 4: ...avy duty industrial handset cord Heavy Duty Urethane Coated Water Tight Membrane Keypad 2 Line X 16 Character Back Lit LCD Display Hearing aid compatible receiver Extended length up to 20ft handset cord Contact Guardian Sales for details Cable Entrances Includes 1 cable gland Support for two additional glands for external peripherals Mounting Simple field installation desktop or wall mount Each MI...

Страница 5: ...ontrols Front Panel LED displays merged zones Front and back panel access to system audio controls and configuration Support Five Zones can be expanded to ten zones Up to 6 Master Control Stations Alarm tone generator Telephone interface module Alarms Remote Alarm Control and Monitor System Summary Alarm Support for Data Communications Monitoring Support for door alarm loop power monitoring Option...

Страница 6: ...rogramming Operation Merge Isolate Zone Control System Figure 1 System Block Diagram 12 2 310mm 5 2 132mm 2 25 57mm 19 0 483mm 18 3 465mm R0 125 R3mm Telecom Inc Guardian MICAB MERGE ISOLATE CABINET Figure 2 Dimensions MICON MICAB Page 6 ...

Страница 7: ...Guardian Telecom Inc Installation Programming Operation Merge Isolate Zone Control System Figure 3 MICON Features Figure 4 MICON Desk Top Mounting Figure 5 MICON Wall Mounting Page 7 ...

Страница 8: ... LOGIC INPUT ALARM LOGIC OUTPUT A ALARM LOGIC OUTPUT B TALK PAGE TALK PAGE TALK PAGE TALK PAGE TALK PAGE LINE Z ADJUST LINE Z ADJUST LINE Z ADJUST LINE Z ADJUST LINE Z ADJUST Figure 6 Back Panel Wiring Connections SEE DETAIL 1 JP3 JP4 JP2 JP5 JP1 F2 154 R 17 R 60 R DETAIL 1 MERGED ZONE INDICATOR LED R17 Data Threshold Pot R154 Mixed Line Level Pot R60 Merged Page Line Level Pot Refer to Figure 9 f...

Страница 9: ... Merged Page Line B 5 Data Signal A 6 Data Signal B 7 24VDC 8 VDC Ground 9 Mixed Signal A 10 Mixed Signal B Note Cable has one spare pair of conductors Figure 8 MICON PCB Layout JP1 Merged Talk Line Impedance Control Position Pins Description 1 2 PTTI Not Installed 2 3 PTTI Installed or Slave MICAB Configuration JP 2 3 4 Master Slave Control Position JP2 JP3 JP4 Pins Description 1 2 Master MICAB S...

Страница 10: ...Logic Outputs 8 VDC Ground Pin Function 9 Mixed Signal A 1 Alarm I P 1 10 Mixed Signal B 2 Alarm I P 2 3 Alarm I P 3 PTTI Connector 4 Alarm I P 4 Pin Function 5 Alarm I P 5 1 Merged Talk Line A 6 Alarm I P 6 2 Merged Talk Line B 7 Alarm I P 7 3 Merged Page Line A 8 Alarm I P 8 4 Merged Page Line B 9 Alarm I P 9 10 Alarm I P 10 11 Alarm I P Common 12 Alarm I P Common Alarm Logic Output Connector A ...

Страница 11: ... If a sixth MICON is required the cable of the sixth MICON may be connected to the MICON 5 connector i e wired in parallel with 5 See MICAB Back Panel Connector Tables CASCADE CONFIGURATION MICON 6 WIRED IN PARALLEL DRY CONTACT O P Page 11 AUX ALARM INPUT CONNECTOR If no dry contact use interface simple interface shown Figure 10 Examples of Auxiliary Alarm Inputs ...

Страница 12: ... n a Page Line J2A J3A PA Page Line Blue Red 18 AWG J2A J3A PB Red Blue Channel J2A J3A 1A Channel 1 Red 18 AWG J2A J3A 1B L Brown Red J2A J3A 2A Channel 2 Violet 18 AWG J2A J3A 2B L Brown Violet J2A J3A 3A Channel 3 Blue 18 AWG J2A J3A 3B L Brown Blue J2A J3A 4A Channel 4 Brown 18 AWG J2A J3A 4B L Brown Brown J2A J3A 5A Channel 5 Yellow 18 AWG J2A J3A 5B L Brown Yellow Group Muting of J2A J3A Mut...

Страница 13: ...les and Installing Multiple Merge Isolate Controllers MICONs Connect the Alarm Generator See AG17 Manual To reduce noise on the Page Talk system 33 Ohm resistors usually installed in a Line Balance Unit LBU are connected across every page talk line in every zone in near the MICAB The MICON provides the loading for all the page and dedicated merge talk lines Resistors for the un merged talk lines s...

Страница 14: ...ad one to six MICONs Adjust this potentiometer as follows Using any MICON as a reference station set the speaker volume to a maximum level Adjust the mixed line level potentiometer until the reference MICON picks up lowest noise Page from one of the Page Talk stations from an isolated zone Listen to the speaker volume on the reference MICON with speaker volume to max Adjust the mixed line level po...

Страница 15: ...nce the system is powered up the MICON is ready for programming its function registers To enter Programming Mode press the PVT key and the LMP TST key simultaneously The LCD display will respond with a greeting message and then the main menu 1 MICON 2 MICAB 3 AlrZn 4 STORE 1 MICON setup Press key 1 while in the main menu to program the existing MICON Once key 1 is selected the screen will display ...

Страница 16: ...d to alter the initial volume 5 Once Reg04 is stored with 0 all the blue zone function keys excluding the PVT key will be disabled Pressing of these keys will result in receiving the deny message on the display 6 Setting Reg05 to 0 or 7 will restore all the registers back to the default settings of the MICON MICAB programming Programming the MICAB is done in two stages First use the MICON station ...

Страница 17: ...B Assertion of its existence in the system Note 1 0 not installed 1 installed 0 Reg14 Merged Time Note 2 1 9 X 10 minutes 6 Reg15 Default Settings Restoring the MICON to the default settings Note 3 0 or 7 to restore default settings 1 Notes 1 All MICON stations and the MICAB slave units have to be programmed to indicate their existence in the system Any MICON station or MICAB slave that is not reg...

Страница 18: ...sfer the registers settings in the MICON to the MICAB Pressing key 4 while in the main menu will cause the MICON to send all the register settings to the MICAB If the master MICAB and the slave MICAB exist they both will be updated with the new settings If the transfer is successful the MICAB will blink all the zone lights Operation Requesting a Merge The caller first sets the Talk Channel Selecto...

Страница 19: ...e all zones MERGE ALL Isolate all zones ISOLATE ALL Trigger alarm ALARM SET alarm Reset alarm from highest priority first ALARM RESET Clear all alarms ALARM CLEAR Test alarm LEDs LAMP TEST Increase speaker receiver volume VOLUME UP Decrease speaker receiver volume VOLUME DOWN Cancel incomplete instructions Merge zones Isolate zones and Alarm trigger instructions PVT Enter into Programming mode PVT...

Страница 20: ... 1 0 I S O A C T V A L A R M S E T 2 A C T V 1 0 The Display is as illustrated below when the MICON is in the report state M R G 1 0 A C T V 1 0 I S O A C T V M R G 1 0 A L A R M 1 2 3 4 5 6 7 8 9 0 Setting and Cancelling Alarms If an AG17 Alarm Tone Generator or similar is connected into the system the Master Controller can generate alarms on the Page lines of selected zones Trigger Alarms To tri...

Страница 21: ...P TST to have a report shown on the LCD display The LMP TST key is also used to check the two Alarm warning LEDs for failure as well as reading the station number of the MICON Connecting to the Telephone System If a PTTI Telephone Interface is integrated into the system it is possible with operator assistance to make or receive calls from a PABX or Central Office To receive calls a telephone exten...

Страница 22: ...e MICABs Apply power to the MICAB again if power source is correct If the MICAB is OK check the MICON cables for short between power pin and ground pin Replace cable if required Connect the MICONs back to the MICAB one at a time to identify the problem MICON Programming Difficulties The MICAB cannot be programmed Be sure all the jumpers on the Master MICAB are set up as the Master MICAB If there i...

Страница 23: ... MICAB From the main programming menu of the Master MICON select 2 MICAB to program the MICAB settings Be sure the problem MICONs are registered in the proper Registers Register 7 to Register 12 Change the MICONs with identical station number to different station numbers The MICAB does not accept instructions from one particular MICON Be sure the MICON connector is properly plugged into the MICAB ...

Страница 24: ... to 1 in order to register the Slave MICAB to the Master MICAB From the main menu select 4 STORE to upload the settings from the MICON to the MICABs If the uploading is done successfully the Zone LEDS on the MICABs will flash once Electrical Hardware Problems No LCD display on MICON Check the ZONE connectors on the back panel of the MICABs for loose wiring Check MICON cable wiring for loose wiring...

Страница 25: ...on 2 and 3 With the Page Talk Station volume control set to a typical level adjust the Merged Page Line potentiometer in the Master MICAB for the proper page speaker volume High volume on all speakers on the Merged Page Line With the Page Talk Station volume control set to a typical level adjust the Merged Page Line potentiometer in the Master MICAB for the proper page speaker volume Cross Talk on...

Страница 26: ... 2AG FAST BLOW MICON INPUT VOLTAGE 24VDC INPUT CURRENT 60mA RESETTABLE AUDIO FREQUENCY RESPONSE 300 3400 HZ PAGING SPEAKER VOLUME 85dB 0 5m ENVIRONMENTAL MICAB DUST WEATHER TIGHT TEMPERATURE 10 to 60 C 14 to 140 F HUMIDITY 0 95 RH Non Condensing CORROSION DUST RESISTANT MICON TEMPERATURE 10 to 60 C 14 to 140 F HUMIDITY 0 95 RH Non Condensing CORROSION DUST RESISTANT Full Gasket Faceplate Keypad ME...

Страница 27: ... 9 4 X 11 1 INCHES NET WEIGHT 5 9 KG 8 6 LBS MOUNTING DESK OR WALL MOUNT TEMPERATURE 10 to 60 C 17 to 140 F HUMIDITY 0 95 RH Non Condensing CORROSION DUST RESISTANT MICON Replacement Parts Part No Description P9003 Handset Assembly P002254 Single Reed Switch P006614 Lock Handset Retainer P006691 Bumper Diameter Urethane P006752 Liquid Crystal Display 2 x 16 Characters P006782 PCBA Merge Isolate Co...

Страница 28: ...High voltages may be present in this product ensure that power is removed before installing performing maintenance or making repairs Service Telephone Number 1 800 363 8010 Toll Free in North America Guardian Telecom provides a customer service telephone number which is toll free within North America If you need assistance when installing or operating this product please call the toll free telepho...

Страница 29: ...m com or by calling the service telephone number given in this manual After providing information on the product the owner and the nature of the problem Guardian will issue a RMA number to be shown on documentation returned with the product In addition to the RMA number shipping documents should include name address and telephone number of the owner along with contact information for the person re...

Страница 30: ...e PTI P5980 Line Balance Assembly LBU Alarm Tone Generator AG 17 P5960 With Relay P5970 Without Relay Acoustic Booths P9010 AB100 Aluminum or Steel full size P9035 AB1000 Glass Reinforced Plastic hood P9029 AB2000 Glass Reinforced Plastic full size Cable P006183 2 Conductor 18AWG Industrial Armored Speaker Cable P006184 2 Conductor 18AWG Industrial Standard Speaker Cable P006217 4 Conductor 18AWG ...

Страница 31: ...Guardian Telecom Inc Installation Programming Operation Merge Isolate Zone Control System Page 31 Typical Page Talk Installation ...

Страница 32: ...dian Telecom Inc Toll free 1 800 363 8010 Phone 403 258 3100 Fax 403 253 4967 www guardiantelecom com E mail sales guardiantelecom com Click to open message box CONNECTED PROTECTED Guardian Telecom Inc 2015 ...

Отзывы: