Chapter 6: System Configuration
Configuring Phone Settings for the Call Out Sequence
The call out phone settings are the parameters the system follows when an alert is set off and a call out
sequence begins.
1. Click on
Menu→System→Settings→Phone settings
.
2. Set the following parameters:
Parameter
Description
Alarm time to start dialing
The amount of time the system waits after an alert is set off and the first
number is called
Number of message repetitions
The number of times the alert message is repeated
No user interaction timeout
The amount of time the system waits between the end of one call and
the beginning of another
Configuring Programmable Outputs
Different programmable outputs can be connected to the system and to the system modules. When cor-
rectly configured and assigned to the correct zones, the outputs can activate or deactivate equipment
during an alert that could potentially save livestock.
Before You Begin
NOTE:
The programmable outputs must first be configured before being assigned to zones.
1. Click on
Menu→System→Output.
2. In edit mode, under the
General
tab, populate the following fields:
• Name of output
• Output location
• Automatic, semi-automatic, or manual power mode
NOTE:
The semi-automatic power mode activates the output when an alert is set off, but the
output can only be closed manually.
• Cal zero (if needed)
• Cal span (if needed)
3. Under the
Limits
tab, enter the high and low alert thresholds in amperes, off and on coil voltage trou-
ble limits, load current trouble limit, and coil voltage.
NOTE:
The high and low alert thresholds in amperes as well as the Cal zero and Cal span can only
be configured on the main system.
Remember
You must activate the output by clicking on the activation button in edit mode, under the
General
tab.
895-00677
Agri Alert 128 Touch
41
Содержание 890-00584
Страница 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Страница 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...
Страница 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...
Страница 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...
Страница 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...
Страница 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...
Страница 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...
Страница 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...
Страница 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...
Страница 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...
Страница 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...
Страница 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...
Страница 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...
Страница 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...
Страница 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...
Страница 108: ...Appendix F Wiring Diagram with Terminals Wiring diagram with a DPST disconnect switch 108 895 00677 Agri Alert 128 Touch...
Страница 109: ...Appendix F Wiring Diagram with Terminals Wiring diagram with a SPST disconnect switch 895 00677 Agri Alert 128 Touch 109...
Страница 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...
Страница 118: ......