41
English (US)
30.4 Inputs/output
Start/stop
External potential-free contact.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Digital
External potential-free contact.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Setpoint signals
• Potentiometer
0-10 VDC, 10 k
˖
(via internal voltage supply).
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 328 ft (100 m).
• Voltage signal
0-10 VDC, R
i
> 50 k
˖
.
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
• Current signal
DC 0-20 mA / 4-20 mA, R
i
= 175
˖
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
Sensor signals
• Voltage signal
0-10 VDC, R
i
> 50 k
˖
(via internal voltage supply).
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
• Current signal
DC 0-20 mA / 4-20 mA, R
i
= 175
˖
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
Internal power supplies
• 10 V power supply for external potentiometer:
Max. load: 2.5 mA.
Short-circuit protected.
• 24 V power supply for sensors:
Max. load: 40 mA.
Short-circuit protected.
Signal relay output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A, cos
˳
0.3 - 1.
Minimum contact load: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
/ 28-12 AWG.
Maximum cable length: 1640 ft (500 m).
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485.
Screened 3-core cable: 28-16 AWG (0.2 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
31. Technical data - three-phase pumps, 15-30 hp
31.1 Supply voltage
3 x 440-480 V - 10 %/+ 10 %, 60 Hz - 3 %/+ 3 %, PE.
Cable: Max. 8 AWG (10 mm
2
)
Use min. 158 °F (70 °C) copper conductors only.
Recommended fuse sizes
Standard as well as quick-blow or slow-blow fuses may be used.
31.2 Overload protection
The overload protection of the E-motor has the same
characteristic as an ordinary motor protector. As an example, the
E-motor can stand an overload of 110 % of I
nom
for 1 min.
31.3 Leakage current
Ground leakage current > 10 mA.
The leakage currents are measured in accordance with EN
61800-5-1.
31.4 Inputs/output
Start/stop
External potential-free contact.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Digital
External potential-free contact.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Setpoint signals
• Potentiometer
0-10 VDC, 10 k
˖
(via internal voltage supply).
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 328 ft (100 m).
• Voltage signal
0-10 VDC, R
i
> 50 k
˖
.
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
• Current signal
DC 0-20 mA / 4-20 mA, R
i
= 250
˖
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
Motor size [hp]
Max. [A]
15
32
20
36
25
43
30
51