21
English (US)
Setting to Min.
Press
continuously to change to the min. curve of the pump
(bottom light field flashes). When the bottom light field is on,
press for 3 seconds until the light field starts flashing.
To return to uncontrolled or controlled operation, press
continuously until the desired setpoint is indicated.
Fig. 23
Min. curve duty
Setting to Max.
Press
continuously to change to the max. curve of the pump
(top light field flashes). When the top light field is on, press for
3 seconds until the light field starts flashing.
To return to uncontrolled or controlled operation, press
continuously until the desired setpoint is indicated.
Fig. 24
Max. curve duty
18.2 Setpoint setting
Set the desired setpoint by pressing the button
or .
The light fields on the control panel will indicate the setpoint set.
See examples in sections
18.2.1 Pump in control mode controlled
(pressure control)
on page
21
and
18.2.2 Pump in control mode
uncontrolled
on page
21
.
18.2.1 Pump in control mode controlled (pressure control)
Example
Figure
25
shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 43 psi (3 bar). The setting range is
equal to the sensor measuring range (see sensor nameplate).
Fig. 25
Setpoint set to 3 bar, pressure control
18.2.2 Pump in control mode uncontrolled
Example
In control mode uncontrolled, the pump performance is set within
the range from min. to max. curve. See fig.
26
.
Fig. 26
Pump performance setting, control mode uncontrolled
19. Setting by means of R100
The pump is designed for wireless communication with Grundfos
remote control R100.
Fig. 27
R100 communicating with the pump via infra-red light
During communication, the R100 must be pointed at the control
panel. When the R100 communicates with the pump, the red
indicator light will flash rapidly. Keep pointing the R100 at the
control panel until the red LED diode stops flashing.
The R100 offers setting and status displays for the pump.
The displays are divided into four parallel menus (see fig.
35
):
0. GENERAL (see operating instructions for the R100)
1. OPERATION
2. STATUS
3. INSTALLATION
The figure above each individual display in fig.
35
refers to the
section in which the display is described.
T
M
00
7
3
4
6
13
04
TM
00
7
345
13
04
T
M
00
7
7
4
3
09
04
H
Q
H
Q
0
6
3
[bar]
T
M
00
7
7
4
6
13
04
TM
02
093
6
050
1
H
Q