42
Connections for the control system – inputs
Connections for the control system – outputs
Analog input for flow meter
Current input 0(4)-20 mA
Load: 50
Ω
Analog input
Chlorine dioxide concentration
Measuring cell (optional)
Pt100 water temperature sensor
in the measuring cell
Contact input
(compound-loop control)
Contact water meter
Maximum 50 pulses/second
Maximum voltage: 13 V
External input
stop
For process enabling and for
external error
mV input
pH or redox
55, 56, H
2
O
Sample-water deficiency sensor
measuring cell
Maximum voltage: 13 V
Switching input K1
Reactor water supply to level K1
Switching input K2
Reactor HCl supply level
Switching input K3
Reactor NaClO
2
supply level
Switching input K4
Reactor water supply to level K4
Switching input K5
Reservoir tank level (batch)
Empty signal
Switching input K6
Reservoir tank level (batch)
Maximum level
Switching input K7
HCl container level
Contact open
Æ
pre-empty signal
HCl
Switching input K8
Container level
Contact open
Æ
empty signal HCl
Switching input K9
NaClO
2
container level
Contact open
Æ
pre-empty signal
NAClO
2
Switching input K10
NaClO
2
container level
Contact open
Æ
empty signal
NAClO
2
Analog output
mA out, 0(4)-20 mA
Current output
Control
Analog output for external
device (proportional to ClO
2
concentration)
Current output
Measured value for check
measurements
0(4)-20 mA
Load: 500
Ω
Solenoid valve for water
supply
Relay 1
HCl pump
Relay 2
NaClO
2
pump
Relay 3
Alarm relay (changeover
contact)
Potential-free output
Relay 4
Warning relay
Potential-free output
Relay 5
ClO
2
dosing pump
Relay 6