40
6. Technical data
6.1 Identification
Fig. 17
Nameplate for OCD-162-5-D/G
6.2 Technical data
Performance and consumption data
Temperatures and humidity
Dimensions and weight
Permissible chemicals
*) All technical data refer to the nominal concentrations. In
operation, deviations up to ± 10 % of the chemicals
concentrations are permissible. They can, however, change the
performance data of the system specified here.
Materials
T
M
03
69
57
45
06
Pos.
Description
1
Type designation
2
Product name
3
Model
4
Serial number
5
ClO
2
production capacity
6
Product number
7
Country of origin
8
Year and week of production
9
Marks of approval, CE mark, etc.
10
Voltage (V)
11
Frequency (Hz)
12
Power consumption
13
Safety instruction: Please read this manual
OCD-162-5:
ClO
2
production capacity
5 g/h
OCD-162-10:
ClO
2
production capacity
10 g/h
Concentration of the chlorine dioxide
solution
Approximately 2 g/l
(2000 ppm)
OCD-162-5:
HCl component consumption
Approximately 0.17 l/h
OCD-162-10:
HCl component consumption
Approximately 0.37 l/h
OCD-162-5:
NaClO
2
component consumption
Approximately 0.14 l/h
OCD-162-10:
NaClO
2
component consumption
Approximately 0.30 l/h
Dilution water at 3-6 bar
OCD-162-5
OCD-162-10
Quality in accordance with EU
drinking water ordinance TrinkwV
2001
Approximately 2.3 l/h
Approximately 4.8 l/h
Maximum back pressure for ClO
2
dosing pump (5 g/h)
DMI 50Hz: OCD-162-5-D/G
DMI 60Hz: OCD-162-5-D/H
DDI 50Hz: OCD-162-5-P/G(H)
DDI 60Hz: OCD-162-5-P/G(H)
9 bar
6 bar
10 bar
10 bar
OCD-162 5D/G
162-005-10000
5/N: 07/64064
5g/h, 230V, 50/60Hz, 850Watt
95702474P1107380764064
1
3
4
7
8
9
6
2
5
1
2
11
10
13
Maximum back pressure for ClO
2
dosing pump (10 g/h)
DMI 50Hz: OCD-162-10-D/G
DMI 60Hz: OCD-162-10-D/H
DDI 50Hz: OCD-162-10-P/G(H)
DDI 60Hz: OCD-162-10-P/G(H)
7 bar
5 bar
10 bar
10 bar
Permissible relative air humidity
(no condensation)
Maximum 80 %
Permissible ambient temperature
+5 °C to +35 °C
Permissible dilution water operating
temperature
+10 °C to +30 °C
Permissible component operating
temperature (chemicals)
+10 °C to +35 °C
Storage temperature of the system
(not connected)
–5 °C to +50 °C
Storage temperature of chemicals
(not connected)
+5 °C to +40 °C
Permissible height above sea level,
where the system is allowed to be
operated
5000 m
System frame with cover
W x H x D
765 x 766 x 330 mm
Gross weight (without collecting trays)
30 kg
Net weight (without collecting trays)
26 kg
Distance between bottom edge of
frame and floor
Approximately 1 m
Collecting trays
W x H x D
485 x 270 x 550 mm
Collecting trays
2 x 5.5 kg
Permissible concentration of the
NaClO
2
solution
7.5 % *) by weight
Permissible concentration of the HCl
solution
9.0 % *) by weight
Total length of suction line including
suction lance
130 cm
System frame
PE
Cover
EPP
Reactor/reservoir tank
PVC
Hoses
PTFE/PE
Seals
FPM/PTFE/FKM
Dosing head on pumps
PVC