background image

10

9. Parts list

Fig. 11

10. Technical data

10.1 Sound pressure level

For sound pressure level, see installation and operating instruc-
tions for CR pumps.

The sound pressure level for a number of pumps can be calcu-
lated as follows:

L

max.

= L

pump

 + (n - 1) x 3.

L

max.

= Maximum sound pressure level.

L

pump

= Sound pressure level for one pump.

n

= Number of pumps.

10.2 Hydraulic data

Minimum pre-pressure:

The minimum pre-pressure “H” in metres head required to avoid 
cavitation in the pumps is calculated as follows:

H = p

b

 x 10.2 - NPSH - H

f

 - H

v

 - H

s

p

b

 =

Barometric pressure in bar.
Barometric pressure can be set to 1 bar.

NPSH =

N

et 

P

ositive 

S

uction 

H

ead i metres head

(to be read from the NPSH curve at the highest flow).
See installation and operating instructions for
CR pumps.

H

f

 =

Friction loss in suction pipe in metres head.

H

v

 =

Vapour pressure in metres head, t

m

 = liquid 

temperature.
See installation and operating instructions for
CR pumps.

H

s

 =

Safety margin of minimum 0.5 metres head.

10.3 Electrical data

Supply Voltage: 3 x 400 V +6%/–10%, 50 Hz, PE. 

Pos.

Description

Number

1

Suction manifold

1

2

Discharge manifold

1

3

Base frame

1

4

Stand

1

5

Control box

1

6

CR pump

2-4

7

Non-return valve

1 per pump

8

Isolating valve

2 per pump

9

Pressure switch

1 per pump

10

Pressure gauge

1

T

M

00

 97

41

 03

97

Hydro 1000

5

10

4

6

2

9

1

8

7

3

Terminal 

designation 

or number

Function CS 1000

Technical data

J1

1

Input for thermal relay 
pump 1

2

Input for thermal relay 
pump 2

3

Input for thermal relay 
pump 3

4

Input for thermal relay 
pump 4

5

6

Common terminal for 
multiplug J1

J2

1 - 2

Input for dry-running pro-
tection

3 - 4

Input for maximum pres-
sure protection

5 - 6

Input for pressure switch 1

7 - 8

Input for pressure switch 2

9 - 10

Input for pressure switch 3

11 - 12

Input for pressure switch 4

J3

1 - 2

Output for contactor K1

AC 24 V

3 - 4

Output for contactor K2

AC 24 V

5 - 6

Output for contactor K3

AC 24 V

7 - 8

Output for contactor K4

AC 24 V

J5

1 - 2

Electricity supply for 
CS 1000

AC 24 V

3 - 4

Electricity supply for 
CS 1000

AC 18 V

5 - 6

Electricity supply for 
CS 1000

AC 8 V

J6

1 - 3

Fault relay

Potential-free 
changeover 
contacts.
Maximum con-
tact load: 
250 V / 3.0 A, 
AC 1

Subject to alterations.

Содержание Hydro 1000

Страница 1: ...Hydro 1000 Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...tives on the approximation of the laws of the EC Member States relating to Machinery 98 37 EC Standard used EN ISO 12100 Electromagnetic compatibility 89 336 EEC Standards used EN 61 000 6 2 and EN 61...

Страница 3: ...rks blocks of flats hotels industry hospitals schools etc 1 2 Operating conditions Liquid temperature Maximum 50 C Ambient temperature 0 C to 40 C Operating pressure Maximum 10 bar Minimum and maximum...

Страница 4: ...s connected Dry running alarm The red indicator light is on when the dry running alarm is activated The light goes out when the alarm is reset If automatic resetting is chosen the indica tor light goe...

Страница 5: ...en the inlet pressure level drops below the set value the pumps are cut out When the correct pressure level value is restored the pumps can be reset to operation auto matically or manually 4 5 Priming...

Страница 6: ...6 Note A pilot pump is the pump that starts first stops last is generally smaller than the other pumps smaller flow higher head is not to be alternated must be installed in position P1 Before changin...

Страница 7: ...more pumps will be cut in until the performance of the pumps in operation cor responds to the requirements When the water consumption falls the discharge pressure rises to the cut out pressure and th...

Страница 8: ...8 Pump 1 will now start 9 Check the direction of rotation of the pump In case of incor rect rotation interchange two phases of the electricity supply 10 Vent the pump while slowly opening its discharg...

Страница 9: ...e pressure Check the diaphragm tank precharge pressure 3 Frequent starts and stops a Incorrect setting of time delay TR 2 Set the time delay TR 2 accordingly b Incorrect setting of pressure switch Inc...

Страница 10: ...a Supply Voltage 3 x 400 V 6 10 50 Hz PE Pos Description Number 1 Suction manifold 1 2 Discharge manifold 1 3 Base frame 1 4 Stand 1 5 Control box 1 6 CR pump 2 4 7 Non return valve 1 per pump 8 Isola...

Страница 11: ...Sasso 4 I 20060 Truccazzano Milano Tel 39 02 95838112 Telefax 39 02 95309290 95838461 Japan GRUNDFOS Pumps K K 1 2 3 Shin Miyakoda Hamamatsu City Shizuoka pref 431 21 Phone 81 53 428 4760 Telefax 81...

Страница 12: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96413144 0405 GB Repl 96413144 0902...

Отзывы: