English (GB)
35
9.12 Alarm simulation register block
See alarm simulation example in section
9.13 User register block
00529
Bit 0: Subpump4WarningsWarningsPhaseSequence
Phase sequence reversed
Bit 1: Subpump4WarningsOvervoltage
Overvoltage
Bit 2: Subpump4WarningsUndervoltage
Undervoltage
Bit 3: Subpump4WarningsOverload
Overload
Bit 4: Subpump4WarningsBlockedMotor
Blocked motor or pump
Bit 5: Subpump4WarningsAlarmBit5
-
Bit 6: Subpump4WarningsMotorTemperature
Motor temperature
Bit 7: Subpump4WarningsElectronicTemperature
Temperature, control electronics
Bit 8: Subpump4WarningsTermoRelay1
Temperature relay 1 in motor, for example Klixon
Bit 9: Subpump4WarningsTermoRelay2
Temperature relay 2 in motor, for example thermistor
Bit 10: Subpump4WarningsVerificationError
Verification error, code area (ROM, FLASH)
Bit 11: Subpump4WarningsAlarmBit11
-
Bit 12: Subpump4WarningsSensorFault
Sensor fault
Bit 13: Subpump4WarningsAlarmBit13
-
Address Register name
Scale
Description
Address Register name
Scale
Description
00701
Simulation.AlarmCode
Enum
The Grundfos-specific alarm code to simulate.
See section
00702
Simulation.WarningCode
Enum
The Grundfos-specific warning code to simulate.
See section
00703
Bit 0:
Simulation.Activate
Bool
Activation of alarm or warning simulation.
0: Deactivate simulation
1: Activate simulation.
00704
Bit 0:
Simulation.Active
Bool
Status of alarm or warning simulation.
0: Simulation not active
1: Simulation active.
Address
Register name
Scale
Description
00751-00800
UserRegisters
Unscaled
This area is for device labelling by the user.
The CIU unit will not modify this area.
The user area values are stored in the device and remain after a
power-off.