English (GB)
19
9.3 CIM status register block
Registers in this block can be read by means of function codes
0x03 and/or 0x04. They are read-only. Use this block for various
kinds of fault finding.
9.4 Cellular network real time clock
Address Register name
Description
CIM
200
CIM
260
CIM
500
00021
GENIbusCRCErrorCnt
Holds a CRC error counter for the GENIbus connection to the product.
●
●
●
00022
GENIbusDataErrorCnt
Holds a data error counter for the GENIbus connection to the product.
●
●
●
00023
VersionNumber
A Grundfos-specific version number. This is an unsigned integer value.
●
●
●
00024
ActualModbusAddress
Holds the current Modbus slave address of the device.
Valid value range: 1…247.
●
●
●
00025
00026
GENIbusTXcountHI
GENIbusTXcountLO
Holds a transmit counter for the total number of telegrams sent to the
product on the GENIbus connection.
●
●
●
00027
00028
GENIbusRXcountHI
GENIbusRXcountLO
Holds a receive counter for the total number of telegrams received from the
product on the GENIbus connection.
●
●
●
00029
GeneralStatus
Bit 0: ScadaPinCodeEnabled
PIN code functionality.
0: No PIN code required
1: PIN code required to perform remote control and configuration.
Activation of SCADA PIN code protection takes place via the SMS
command "SCADACODE". See "CIM 260 SMS commands" which you can
download from Grundfos Product Center.
-
●
-
GeneralStatus
Bit 1: WriteAccess
Remote write access.
0: No write access, the PIN code is incorrect.
1: Full write access, the PIN code is either correct or not enabled.
00030
UnitFamily
Grundfos product family.
●
●
●
00031
UnitType
Grundfos product type.
●
●
●
00032
UnitVersion
Grundfos product version.
●
●
●
00033
BatteryState
State of battery
0: Battery not present
1: Battery must be replaced
2: Battery charging
3: Battery needs charging, but temperature too high
4: Battery needs charging, but temperature too low
5: Battery low
6: Battery OK
255: Battery state not available
-
●
-
00034
ProductSoftwareVersionHI
Product software version (BCD diget 1-4 aa.bb)
●
●
●
00035
ProductSoftwareVersionLO
Product software version (BCD diget 5-8 cc.dd)
●
●
●
00036
ProductSoftwareDayMonth
Product software date (BCD ddmm)
●
●
●
00037
ProductSoftwareYear
Product software date (BCD yyyy)
●
●
●
Address
Register name
Description
CIM
200
CIM
260
CIM
500
00080
SetUNIXRealTimeClockHI
Set real time clock (32 bit UNIX format)
Triggered on value change
-
●
-
00081
SetUNIXRealTimeClockLO
-
●
-
00082
SetRtcSecond
Set real time clock - seconds
-
●
-
00083
SetRtcMinute
Set real time clock - minutes
-
●
-
00084
SetRtcHour
Set real time clock - hours
-
●
-
00085
SetRtcDay
Set real time clock - day
-
●
-
00086
SetRtcMonth
Set real time clock - month
-
●
-
00087
SetRtcYear
Set real time clock - year
-
●
-
00088
Bit 0: SetRtc
Triggers setting of real time clock - s/m/h/d/m/y format
-
●
-
00089
StatusUNIXRealTimeClockHI
Real time clock (32 bit UNIX format)
-
●
-
00090
StatusUNIXRealTimeClockLO
-
●
-
00091
StatusRtcSecond
Real time clock - seconds
-
●
-
00092
StatusRtcMinute
Real time clock - minutes
-
●
-
00093
StatusRtcHour
Real time clock - hours
-
●
-
00094
StatusRtcDay
Real time clock - day of month
-
●
-
00095
StatusRtcMonth
Real time clock - month
-
●
-
00096
StatusRtcYear
Real time clock - year (after 2000)
-
●
-
00097
Bit 0: StatusSetRTCAck
Acknowledge of set RTC command
-
●
-