Eng
lish (US)
20
8.3 DLC, float-switch-controlled option
8.4 DLC, transducer-controlled option
8.5 Additional options
**Enclosure adder is required
Note: Seal-failure sensor(s), overtemperature sensor(s) are standard. Condition messages, such as run time, alarms and pump
cycles are displayed on the HMI operating panel.
Description
Phase
Voltage
[VAC]
Motor shaft
power
[hp]
Overload range
[A]
Main disconnect
switch required
[A]
Product
number
DLC.208/230.B.1-FC
1
208/230
2.0
10.0 - 40.0
25
99165672
DLC.208/230.A.3.A-FC
3
208/230
1.5 - 1.8
2.0 - 6.3
20
99107783
DLC.208/230.B.3.B-FC
3
208/230
2.0 - 3.0
5.7 - 18.9
20
99107784
DLC.208/230.B.3.C-FC
3
208/230
2.0 - 7.5
9.0 - 30.0
50
99107785
DLC.208/230.C.3.D-FC
3
208/230
8.0 - 10.0
15.0 - 45.0
75
99107786
DLC.208/230.D.3.D-FC
3
208/230
12.5 - 15.0
15.0 - 45.0
120
99107787
DLC.460.E.3.A-FC
3
460
1.5 - 4.0
2.0 - 6.3
20
99107788
DLC.460.F.3.B-FC
3
460
5.5 - 10.0
5.7 - 18.9
40
99107789
DLC.460.D.3.C-FC
3
460
12.5 - 15.0
9.0 - 30.0
50
99107790
DLC.575.G.3.E-FC
3
575
1.5
1.6 - 2.5
15
99153145
DLC.575.H.3.F-FC
3
575
1.8 - 3.0
2.5 - 4.0
15
99153146
DLC.575.I.3.G-FC
3
575
4.0 - 5.5
4.0 - 6.3
20
99153147
DLC.575.J.3.H-FC
3
575
7.5
6.0 - 10.0
25
99153148
DLC.575.C.3.I-FC
3
575
8.0 - 10.0
9.0 - 14.0
30
99153149
DLC.575.D.3.J-FC
3
575
12.5 - 15.0
13.0 - 18.0
40
99153150
Description
Phase
Voltage
[VAC]
Motor shaft
power
[hp]
Overload range
[A]
Main disconnect
switch required
[A]
Product
number
DLC.208/230.B.1-PT
1
208/230
2.0
10.0 - 40.0
25
99165674
DLC.208/230.A.3.A-PT
3
208/230
1.5 - 1.8
2.0 - 6.3
20
99107067
DLC.208/230.B.3.B-PT
3
208/230
2.0 - 3.0
5.7 - 18.9
20
99107068
DLC.208/230.B.3.C-PT
3
208/230
2.0 - 7.5
9.0 - 30.0
50
99107069
DLC.208/230.C.3.D-PT
3
208/230
8.0 - 10.0
15.0 - 45.0
75
99107070
DLC.208/230.D.3.D-PT
3
208/230
12.5 - 15.0
15.0 - 45.0
120
99107071
DLC.460.E.3.A-PT
3
460
1.5 - 4.0
2.0 - 6.3
20
99107072
DLC.460.F.3.B-PT
3
460
5.5 - 10.0
5.7 - 18.9
40
99107073
DLC.460.D.3.C-PT
3
460
12.5 - 15.0
9.0 - 30.0
50
99107074
DLC.575.G.3.E-PT
3
575
1.5
1.6 - 2.5
15
99153157
DLC.575.H.3.F-PT
3
575
1.8 - 3.0
2.5 - 4.0
15
99153158
DLC.575.I.3.G-PT
3
575
4.0 - 5.5
4.0 - 6.3
20
99153159
DLC.575.J.3.H-PT
3
575
7.5
6.0 - 10.0
25
99153160
DLC.575.C.3.I-PT
3
575
8.0 - 10.0
9.0 - 14.0
30
99153161
DLC.575.D.3.J-PT
3
575
12.5 - 15.0
13.0 - 18.0
40
99153162
SLC and DLC
Product number
**Battery backup with charger (for alarm only)
Consult factory
**Intrinsically safe relay for float inputs with UL698A Listing (FC only)
**Intrinsically safe barrier/relay for pressure transducer and backup floats, UL698A (PT only)
Padlockable main disconnect switch
Phase monitor with fusing
304 Stainless steel panel
Enclosure adder
Содержание 99107059