23
English (US)
9.5 Digital input and output screens
The pump control panel will activate various input and output screens as it operates. See fig.
. These screens are helpful when
installing and troubleshooting the control panel. The input screens will vary according to the mode of operation of the panel.
See the following tables to identify the conditions that activate the various screens.
Fig. 20 Example, digital input and output screens
9.5.1 SLC, float-switch-controlled option
9.5.2 SLC, transducer-controlled option
TM
06 72
17 291
6
Activated input
Inputs 1-9
Inputs 10-19
Inputs 20-24
Input screen
Output screen
Outputs 1-9
Outputs 10-16
Activated output
Input screen
Function
Activation condition
1
Pump Off Float
Float switch in up position
2
Pump On Float
Float switch in up position
3
High Level Alarm Float
Float switch in up position
4
Push To Silence
Push button is pressed.
5
Pump Fault
Pump seal-failure sensor, overtemperature sensor, or overload protection
has tripped.
Output screen Function
Activation condition
6
Pump
Pump is called to run.
7
Alarm Light
Alarm light is activated.
8
Audible Alarm
Audible alarm is activated.
Input screen
Function
Activation condition
1
Redundant Off and Low Level Alarm Float Float switch in up position
2
High Level Float
Float switch in up position
3
Push to Silence
Push button is pressed.
4
Pump Fault
Pump seal-failure sensor, overtemperature sensor, or overload protection
has tripped.
5
Not Used
NA
6
Not Used
NA
7
Transducer (analog signal)
4-20 mADC
Output screen Function
Activation condition
8
Pump 1
Pump is called to run.
9
Pump 2
Pump is called to run.
10
Level Alarm Light
Level alarm condition exists.
11 Audible
Alarm
Audible alarm is activated.