11. Fault finding the product
12. Technical data
WARNING
Arc flash and electric shock hazard
Death or serious personal injury
- Wear appropriate personal protective equipment
(PE) and tools while working on this equipment.
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, pumps,
pits, etc., make sure that the power supply has
been switched off and that it cannot be
accidentally switched on.
CAUTION
Toxic material
Minor or moderate personal injury
- Before starting any work on pumps used to pump
liquid which could be constituted as being
hazardous to health, clean and vent pumps, pits,
etc. thoroughly according to local regulations.
See also the Installation and Operating Instructions
for the pump in question.
Fault
Cause
Remedy
1. The pump does not run.
a) No power supply.
Without battery back-up:
None of the indicator lights are on.
With battery back-up (accessory):
The indicator lights are on.
Switch on the power supply.
b) The Automatic/Manual/Off toggle switch is in the
Off position.
Push the Automatic/Manual/Off toggle switch to
Manual or Automatic.
c) The control circuit fuses are blown.
Check and eliminate the cause.
Replace the control circuit fuses.
d) The overload relay has cut out the pump (the red
indicator light for pump fault is permanently on).
Check the pump/pit.
e) The overtemperature sensor in the motor windings
has cut out the pump. The red indicator light for
pump fault is flashing.
Allow the pump to cool. After the pump cools, it
will restart automatically unless the SLC or DLC
toggle switch has been set to Manual. If so, the
Automatic/Manual/Off toggle switch must be
pushed into position Off for a short period.
If the pump cut off was caused by choked level
switches, these must be cleaned or replaced.
f)
The control circuit for the overload relay has been
broken or fails (the green indicator light indicating
pump operation is permanently on).
Check the control circuit.
g) The motor/supply cable is defective.
Check motor and cable.
h) The float switch(es) is (are) defective.
Check cables and float switches.
2. The pump is starting/
stopping too frequently.
a) The float switch(es) is (are) defective.
Check cables and float switches frequently.
Voltage tolerance
-15 % / +10 % of rated voltage (3 x 208/230 VAC, 3 x 460 VAC), 3 x 575 VAC)
+10 % / -1 % of rated voltage (1 x 230 VAC)
Mains frequency
60 Hz
Ambient temperature
During operation: -22 °F to +122 °F (-30 °C to +50 °C) (must not be exposed to direct sunlight)
During transport and storage: -22 °F to +140 °F (-30 °C to +60 °C)
Enclosure class
NEMA4X
Outputs for alarm devices
Maximum 120 VAC / maximum 8 A / minimum 10 mA / AC 1
NO/NC contact
Approvals
Listed per UL 508A