9.9.2 Block names, SLC, transducer-controlled option
The following block names are used for SLC, transducer-controlled option.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your
application.
Example, changing the adjustable parameter screens, SLC transducer-controlled option
See the below example of the Off/On level settings and how to navigate through the screens.
Screen names
Description
Units of
measurement
Default
setting
On Level
Tank level at which the lead (duty) pump starts.
feet
12.0
Off Level
Tank level at which the pump stops.
feet
9.0
High Level Alarm
Tank level at which the high-level alarm is activated.
feet
14.0
Low Level Alarm
Tank level at which the low-level alarm is activated.
feet
3.0
Xducer Range
The full range of the transducer (NOT the tank height), i.e. the 4-20 mA
signal from the transducer equals 0 - Xducer Range.
feet
15.0
Xducer Offset
The distance between the bottom of the transducer and the bottom of the
tank.
feet
0.5
Minimum Run Time
The minimum pump run time for an automatic cycle.
seconds
2.0
High Level Pump Run Time The minimum pump run time during a high-level state.
minutes
1.0
High Level Alarm Delay
The time between the high-level state and alarm status.
seconds
5.0
Step
Action
Illustration
1
• Press the "ESC" button and hold it down until the blinking underscore appears
(approximately 3 seconds).
• Then press the "OK" button.
• The blinking underscore will change to a blinking cursor.
TM
06 76
19 371
6
2
• Press the "
" or "
" button to move the cursor to the digit(s) that need to be changed;
note that on the On Level setting the decimal goes away but the tenths spot is still
active.
• To change the value, use the "
" or "
" buttons.
• When the new value has been entered, press "OK".
• The cursor will change back to an underscore.
TM
06 762
0 371
6
3
• At this point, the blinking underscore should still be present; by pressing the "
"
button you can scroll to the lower value and repeat steps 1-2 to change its value.
• When finished, press "OK" and the cursor will change to an underscore.
• Press the "ESC" button twice to exit Parameter mode.
TM
06
76
21
37
16