9. Functions
The SLC and DLC control panels include an easy-to-use
programmable logic unit that incorporates many timing and logic
functions.
The pump control panel features alarm and data screens to assist
with monitoring and troubleshooting. The up- and down-arrow
buttons allow you to navigate between the screens.
See the following table and screen navigation section for more
details.
Alarm screens will only be displayed when alarms are active. The
alarm screen shows the date and time when the alarm started.
9.1 SLC, float-switch-controlled option
9.2 SLC, transducer-controlled option
Alarm screen Alarm text
Description
1
High Level Alarm
High-level alarm
2
Pump Fail Alarm
Pump-failure alarm
Data screen
System data
Description
3
Pump CT & ETM
Pump cycles are shown at the top of the screen and the pump run time beneath.
4
High Lvl CT
High-level alarm events
5
Power Fault Counters
Power failures are shown at the top of the screen and the hours in service beneath.
6
Pump Fault Counters
Pump-failure events
Alarm screen Alarm text
Description
1
Xducer Sig
Is activated when the transducer signal is below 3 mA.
2
High Level Alarm
When lifted, this float switch activates the alarm indication on the screen and the audible
alarm.
3
Low Level Alarm
When lowered, this float switch stops the pump and activates the indication on the
screen.
4
Pump Fail Alarm
Is activated when the pump overtemperature sensor, seal-failure sensor or overload
relay has tripped.
Data screen
System data
Description
5
Current Tank Level
Liquid level in tank or pit in feet
6
Pump CT & ETM
The pump cycle counter is shown at the top of the screen and the pump run time in
minutes beneath.
7
High Lvl CT & Low Level CT
The high-level alarm counter is shown at the top of the screen and low-level alarm
counter beneath.
8
Power Faults & Operating Hr
The power failure counter is shown at the top of the screen and operating hours beneath.
9
Transducer Signal
"Raw value of transducer reading", in mA
10
On/Off Level Settings
Pump-on and -off level setpoints
11
High/Low Level Settings
High- and low-level alarm setpoints
12
Transducer Input
Transducer range and offset settings
13
Minimum Run Time
Minimum pump run time per cycle
14
High Level Pump Run Time
Minimum high level pump run time per cycle
15
High Level Alarm Delay
Elapsed time between high level point and alarm activation