Iron / manganese removal
Demanganisation system GENO-mat MN-Z
Order no. 095 153 048-inter Edited by: nkes-mrie G:\BA-153048-INTER_095_GENO-MAT_MN-Z.DOCX
18
1.1
Water installa-
tion
It is imperative that you comply with certain regulations when in-
stalling the GENO-mat MN-Z demanganisation system. Additional
recommendations are given in order to facilitate the handling of the
system. The installation instructions described below are also illus-
trated in fig. D-2.
Mandatory regulations
The installation of the GeNO-mat MN-Z demanganisation system
represents a major interference with the drinking water system.
Therefore, only authorised experts may install such systems. In Ger-
many, the installation company must be registered in a water com-
pany installation directory as per §12(2) AVBWasserV (German Ordi-
nance on General Conditions for the Supply of Water).
Observe local and general installation guidelines.
Provide a drain connection to discharge the backwash water.
The installation room must have a floor drain (DN 100). If no floor
drain is available, a corresponding water stop device has to be in-
stalled.
Observe the flow direction!
Warning!
Floor drains that discharge to a lifting system will not work
in case of a power failure.
Recommendations
Provide a sampling valve and a pressure gauge directly upstream
and downstream of the GeNO-mat MN-Z demanganisation system
(0 -10 bar). This simplifies the sampling for the regular determina-
tion of the iron concentration (functional check).
1.2
Electrical instal-
lation
A shock-proof plug is adequate for the electrical connection. How-
ever, it must comply with the specifications given in table D-1, may
not be further than 1.20m away from the GeNO-mat MN-Z deman-
ganisation system and must carry constant voltage (do not couple
with light switch)!