Filtration/Deacidification
Filter systems GENO-mat KF-Z / MS-Z / AK-Z
Deacidification systems GENO-mat TE-Z
Order no. 035 129 950-inter Edited by: nkes-mrie G:\BA-129950-INTER_035_FILTERANLAGEN_GENO-MAT.DOCX
32
3.1.1 Timer settings
For the disinfection the corresponding regeneration tank and the
appropriate regeneration agent are required (refer to 3.1 prepara-
tion of the regeneration agent).
Flip the cover of the control valve to the side.
Release a manual regeneration (refer to chapter F, item 1.4).
Flip the timer to the right and wait for 10 minutes until limit switch
1 is free (Fig. G-1, picture 1) and the actuator of the control piston
has stopped.
Unplug mains plug.
Open the ball valve on the back of the control valve and suck the
regeneration agent from the connected regeneration tank.
Close the ball valve again after the regeneration agent has been
completely sucked off.
Reconnect mains.
Wait until limit switch 1 is pressed again (Fig. G-1,
picture 2) and the actuator of the control piston has stopped.
Unplug mains plug.
Flush for at least 30 minutes in order to wash out all residues of
the disinfection agent from the filter bed.
Reconnect mains.
The filter/deacidification systems are ready for operation again
when the limit switches 1 and 2 are free (Fig. G-1, picture 3).
Screw cover back on.
Limit switch 1
Limit switch 2
Limit switch 2
Limit switch 2
Limit switch 1
Limit switch 1
Programmer dial
Programmer dial
Programmer dial
Fig. 1
Fig. 2
Fig. 3
Fig. G-1: Rear of timer