15

6.3 Power on Battery

Power on single battery by pressing POWER button

No, Procedures

Acceptation criteria

1

Close the breaker that 
is connected with 
positive and negative 
power cables.

Breaker in ON position.

2

Press POWER button 
for two seconds and 
observe the LED 
indication on panel.

1. If both RUN and SOC lights turn on 
normal, battery powers on successfully;
2. If ALM light turns red, there is a 
failure and should be fixed before 
powering on again.

Power on single battery by PCS activation

1

Close the breaker that 
is connected with 
positive and negative 
power cables.

Breaker in ON position.

2

PV or mains supply 
powers PCS.

1.PCS in ON position;
2, PCS HMI screen indicates normal 
PV or mains supply input.

3

PCS voltage/wakeup 
signal activates battery.

1. If RUN light and SOC lights on 
battery indicate normal, battery powers 
on successfully;
2. If the ALM light turns red, the 
indication shows a failure. The failure 
shall be fixed before powering on again.

Power on parallel-connected batteries by pressing POWER button

1

Close the breaker that 
is connected with 
positive and negative 
power cables.

Breaker in ON position.

2 Press POWER button 

of any battery for two 
seconds and observe 
the LED indication on 
two panels.

1. If RUN and SOC lights on both batteries 
turn on normal, and the RUN lights on both 
batteries flicker for five times, two batteries 
power on successfully and communication 
between batteries works;
2. If ALM light of one or both batteries turn 
red, there is a parallel failure and should be 
fixed before powering on again.

Power on parallel-connected batteries by PCS activation

1 Close the breaker that 

is connected with 
positive and negative 
power cables.

Breaker in ON position.

2 PV or mains supply 

powers PCS.

1. PCS in ON position;
2. PCS HMI screen indicates normal PV or 
mains supply input.

3 PCS voltage/wakeup 

signal activates battery.

1. If RUN lights and SOC lights on both 
batteries indicate normal, and RUN lights 
on both batteries flicker for five times, 
two batteries power on successfully and 
communication between batteries works;
2. If the ALM light of one battery or 
both batteries turn red, there is a parallel 
connection failure and should be fixed 
before powering on again.

6.4 Power off Battery

* 

Press the POWER button of any battery for two seconds. 

               Five LED lights will flicker for three times, and battery turns off.
* 

Battery will turn off 25 minutes after Network Cable A connection  

               between PCS and battery fails.

Содержание GBLI 6532

Страница 1: ...Date 2020 Version V 0...

Страница 2: ...er Version Date 1 N A Chen Le Shen Zhengbin Li Bing Guo Yihao V1 0 2020 07 24 2 Added the icon read the manual before operating Updated the caution about the two pole breaker Wang Qian Shen Zhengbin G...

Страница 3: ...or or moderate injury Symbol Description WARNING CAUTION Table of Contents 1 Safety 1 1 1 Warning Label 1 1 2 Precautions 2 1 3 Responses to Emergencies 2 1 4 Storage safety 3 1 5 Transportation Safet...

Страница 4: ...on area Risk of electric shock Explosive gas Battery may leak corrosive electrolyte Battery is heavy enough to cause severe injury 1 Safety 1 1 Warning Label Do not reverse polarities Do not expose ba...

Страница 5: ...is dangerous and must be handled with utmost care They are not usable for use and could pose a safety threat to people or property If battery is suspected to be damaged stop any operation and return...

Страница 6: ...ests and Criteria and SN T 0370 2 2009 Part 2 Performance Test of the Rules for the Inspection of packaging for Exporting Dangerous Goods The battery is classified as class 9 dangerous goods and is su...

Страница 7: ...2 2 Function Compared with normal batteries the battery is characterized with better charging and discharging performance longer cycle life and less self discharging loss The build in BMS can monitor...

Страница 8: ...harging Current temperature refere to the cell surface temperature 10 0 21 3A 0 45 104 2A 45 50 85 3A 50 55 32A 9 Norminal Charging and Discharging powern 3 3KW 10 Short Circuit Current 2200A 4ms 11 M...

Страница 9: ...Ground Wall Wall Ground 5 5 500 d 1200 90 500 d 1200 500 d 1200 It is recommended to build sunshade rain shelter to avoid direct exposure to sunlight and rain 3 2 Installation Required Tools Drill Cri...

Страница 10: ...racket to wall Choose alloy drill bit with a diameter of 12mm and install it to a drill Drill in the spots that have been located in step 1 and have at least 60mm drilling depth Clean the soil and dri...

Страница 11: ...ntil the notch locks limiting pin rotate the right latch leftward until the notch locks limiting pin too Leave a minimum clearance of 133mm before the front surface of battery In order to guarantee a...

Страница 12: ...in the drill Drill two holes in the spots that have been confirmed in step 1 Keep the drilling depth as least 60mm Clean the soil and drive expansion tube into hole Move battery back to the place conf...

Страница 13: ...GND ISO 5 Master Select 6 GND ISO 7 GND ISO 8 WKP OUT Item No Link Out 1 COM CANH 2 COM CANL 3 Encode OUT 4 GND ISO 5 Slave Last 6 GND ISO 7 GND ISO 8 WKP OUT 3 Press connecting part with a hydraulic...

Страница 14: ...crimper 4 Connect RJ45 plug with joint sleeve and tighten up sealing sealing nut and joint sleeve 2 Network cable adopts standard 8 core cable Insert eight wires into RJ45 plug Ensure the color of wi...

Страница 15: ...on Steps under Parallel Connection Step 1 Install battery If voltage difference is measured more than 1V the difference shall be adjusted to be less than 1V either by charging the battery with lower v...

Страница 16: ...battery Batteries undergone less than 300 cycles are defined as new batteries WARNING 6 Power on off Battery 6 1 LED Indication There are many technical contents involved in the electrification proce...

Страница 17: ...75 0 SOC 75 1 99 9 SOC 100 SOC Discharge Standby 100 75 1 75 0 50 1 50 0 25 1 25 0 0 LED Indicator light Status Description Dispaly Logics Battery Status Description Light Indication LED1 LED2 LED3 L...

Страница 18: ...n 2 Press POWER button of any battery for two seconds and observe the LED indication on two panels 1 If RUN and SOC lights on both batteries turn on normal and the RUN lights on both batteries flicker...

Страница 19: ...kage zip and decompress it 2 Enter BMS Installation package Volume double click setup exe and run it 3 Execute the default configuration until completing the installation Step 2 Make sure the battery...

Страница 20: ...de file 4 Click Start to Upgrade 5 Upgrade succeeds when progress bar reaches 100 T 86 0755 2747 1942 E service ginverter com W www ginverter com Address No 28 Guangming Road Shiyan Street Bao an Dist...

Отзывы: