MELBURY HE 3800-10000 -
Installation, Use and Maintenance
Page 24 / 36
410821-V11
4.2.3. Boiler support
It is possible to mount the boiler on vibration dampers
(available as option) to reduce noise transmission
caused by vibrations.
figure 9 - With vibration dampers
figure 10 - Without vibration dampers
Melbury HE
3800 4500 5400 6300 7400
8600
10000
Distance wall - boiler body front
D mm
3800 4000
4400
4800
5200
5700
6200
Boiler length
T mm
4350 4590
4990
5409
5859
6401
7002
Distance wall - boiler back
U mm
1150 1150
1150
1150
1150
1150
1150
Distance wall - boiler flank (*)
V mm
1000 1000
1000
1000
1000
1000
1000
Boiler feet length
I mm
2700 2850
3200
4110
4510
4912
5412
Boiler feet width
b mm
1150 1290
1350
1520
1610
1670
1730
Measure
d mm
15
15
15
42
42
42
42
Silent block length
e mm
706 /
562
706
634
634
634
670
670
Silent block width
S mm
50
50
60
75
75
85
85
Number of silent blocks
6 / 2
8
10
12
14
14
16
U-girder width
S1 mm
60
60
65
80
80
90
90
* The dimension can be reduced to 200 mm, as long as
this does not impair the operation of the control panel
and the ability to open a nearby furnace door.
The mounting instructions for the silent blocks can be
found in the separate assembly guide.
After this, you can start installing the connection tubes
on the water and flue gas side.
CAUTION:
Once the boiler is filled up, it will come down by further 3-5 mm.
!