4.4.3. Connecting the burner
The electrical connections of the burner (power supply
and control) are made by the customer in accordance
with the requirements of the burner.
4.5. Turbulators
Thanks to the turbulators, which are to be inserted in
the smoke tubes, the combustion gas temperature can
be controlled.
All smoke tubes in the third pass must equally be
provided with turbulators. These smoke tubes are
those that are open on the rear part, in the direction of
the combustion gas collector.
The mounting instructions can be found in the separate
assembly guide.
Melbury HE
3800 4500
5400
6300 7400 8600
10000
Number of turbulators
54
63
72
80
84
91
99
Outer diameter
Da
mm
72
Edge diameter
d
mm
10
Pitch
A
mm
80
Length
L
mm
3100
figure 11 - Turbulator