background image

2

GB

Application

Thermostat mixers are designed for hot water supplies from 
pressurised storage heaters and offer the highest temperature 
accuracy when used in this way.
Thermostat mixers cannot be used in conjunction with low-
pressure storage heaters.
All thermostat mixers are adjusted at the factory with a flow 
pressure of 3 bar on both sides.
A stopcock (A) must be installed between the mixed water 
outlet of built-in thermostatic mixer without shut-off 
device (34 953) and the draw-off point, see Fig. [1].
For an order number index to the various installation components 
and handle element for the built-in mixer, see Fig. [2].
a = Size of union
b = Part
c = Part No.
When this model is used as a central thermostat, standard 
mixers can be installed at the draw-off points.
In this case, the thermostat mixer supplies hot water to which 
cold water can be added.

The built-in thermostat with shut-off device (34 954) only 
shuts off the upper outlet. An additional stopcock must be 
fitted if the lower outlet is used, see Fig. [2].

Technical Data

• Minimum flow pressure without 

downstream resistances

0.5 bar

• Minimum flow pressure with 

downstream resistances

1 bar

• Max. operating pressure

10 bar

• Recommended flow pressure

1 - 5 bar

• Test pressure

16 bar

• Flow rate at 3 bar flow pressure

34 953

approx. 37.5 l/min.

• 34 954

approx. 24 l/min.

• Max. water temperature at hot water inlet

80 °C

• Recommended max. flow temperature

60 °C

(for energy saving)

• Safety stop

38 °C

Hot water temperature at supply connection min. 2 °C higher 
than mixed water temperature.

• Hot water connection - W - (-H-)

left

• Cold water connection - K - (-C-)

right

• Minimum flow rate

5 l/min

At a flow pressures above 5 bar, we recommend installing a 
pressure reducer in the supply pipe.

Prevention of frost damage

When the domestic water system is drained, the thermostat 
mixers must be drained separately, since non-return valves 
are installed in the hot and cold water connections. The 
complete thermostat assembly and non-return valves must be 
unscrewed and removed.

Preliminary installations

- Prepare wall for mixer.

Drill holes for thermostat mixer and cut slots for pipes.

- Observe the installation depth in accordance with the 

instructions given on the mounting template, see Fig. [3].

x= Face of tiles
y = Front face of mounting template
z = Contact point for spirit level

- Align the thermostat horizontally, vertically and parallel to the 

wall, see Fig. [4] (place a spirit level on the cams or face of 
the mounting template).

- Install built-in thermostat thermostat module in wall and 

connect pipes, see Fig. [5]. The housing is provided with 
pre-drilled holes (B) to facilitate mounting the fitting to the 
wall, see Fig. [4].

- Connecting the pipelines to the thermostat is facilitated by 

the left/right threaded nipple already loosely screwed-on on 
the cold water side, see Fig. [6].

-

Do not solder the connections between the pipes and 
housing

, otherwise the built-in non-return valves may be 

damaged.

- Seal the open outlet with a screw plug.

Note!

-

The hot water supply must be connected on the left

 

(marked W (H) on housing) 

and the cold water supply on 

the right

 (marked K (C) on housing), 

as viewed from the 

operating position.

Checking pipes and thermostatic mixer body for leaks.

Flush pipes thoroughly.

Plaster and tile the wall.

Do 

not

 remove the fitting template before final installation.

Содержание 34 953

Страница 1: ...18 12 7 D 1 NL PL GB S UAE F DK GR E N CZ I FIN H 2 3 4 5 6 8 9 10 11 13 14 15 P 16 17 TR RUS SK SLO 19 20 22 21 HR BG EST LV 23 24 26 25 LT RO 34 954 97 415 031 M 40 560 06 04 34 953 Linie Europlus...

Страница 2: ...ease pass these instructions on to the end user of the fitting S v p remettre cette instruction l utilisateur de la robinetterie Bitte diese Anleitung an den Benutzer der Armatur weitergeben 34 953 34...

Страница 3: ...II 1 min 180 A a b c 1 2 29 800 15mm 29 801 3 4 29 802 18mm 29 803 22mm 29 804 19 845 19 846 2 3 X Y Z B B 4 5 6...

Страница 4: ...ie druck ber 5 bar wird empfohlen in die Versorgungsleitung Druckminderer einzubauen Achtung bei Frostgefahr Bei Entleerung der Hausanlage sind die Thermostate gesondert zu entleeren da sich im Kalt u...

Страница 5: ...tion W H left Cold water connection K C right Minimum flow rate 5 l min At a flow pressures above 5 bar we recommend installing a pressure reducer in the supply pipe Prevention of frost damage When th...

Страница 6: ...nchement d eau chaude W H gauche Branchement d eau froide K C droite D bit minimum 5 l min Dans le cas de pressions statiques sup rieures 5 bars la pose de r ducteur de pression d eau RPE est recomman...

Страница 7: ...enda instalar una v lvula reductora de presi n en la tuber a de alimentaci n Atenci n en caso de peligro de helada Al vaciar la instalaci n de la casa los termostatos deber n vaciarse aparte pues en l...

Страница 8: ...ione min 2 C pi alta di quella dell acqua miscelata Raccordo acqua calda W H a sinistra Raccordo acqua fredda K C a destra Portata minima 5 l min Per una pressione superiore a 5 bar si raccomanda di i...

Страница 9: ...ter min Bij een waterdruk van meer dan 5 bar raden wij aan drukreduceerventielen in de netleiding te monteren Attentie bij vorst Bij het leeg laten lopen van de waterleidingen in huis mag u niet verge...

Страница 10: ...andvattentemperaturen Varmvattenanslutning W H v nster Kallvattenanslutning K C h ger Minimifl de 5 l min Vid ett fl destryck p mer n 5 bar rekommenderas installation av en reducerventil i vattenledni...

Страница 11: ...lslutning K C til h jre Mindste gennemstr mning 5 l min Ved gennemstr mningstryk p over 5 bar anbefales det at montere reduktionsventiler i forsyningsledningen Bem rk ved fare for frost N r anl gget i...

Страница 12: ...lkopling K C h yre Minimum gjennomstr mning 5 l min Ved str mningstrykk over 5 bar anbefales det montere en trykkreduksjonsventil i hovedledningen Ved fare for frost N r husanlegget t mmes m termostat...

Страница 13: ...eampi kuin sekoitetun veden l mp tila L mminvesiliit nt W H vasemmalla Kylm vesiliit nt K C oikealla V himm isl pivirtaus 5 l min Suosittelemme asentamaan sy tt johtoon paineenalennusventtiilin jos vi...

Страница 14: ...Doprowadzenie wody gor cej W H str lewa Doprowadzenie wody zimnej K C str prawa Przep yw minimalny 5 l min Je li ci nienie statyczne przekracza 5 bar to zaleca si wmontowanie reduktora ci nienia W pr...

Страница 15: ...12 UAE...

Страница 16: ...13 GR 3 bar 34 953 1 2 a b c 34 954 2 0 5 bar 1 bar 10 bar 1 5 bar 16 bar 3 bar 34 953 37 5 l min 34 954 24 l min 80 C 60 C 38 C 2 C W H K C 5 l min 5 bar 3 x y z 4 5 4 6 W H K C...

Страница 17: ...2 C vy ne teplota sm en vody P ipojen tepl vody W H vlevo P ipojen studen vody K C vpravo Minim ln pr tok 5 l min P i statick ch tlac ch vy ch ne 5 bar doporu ujeme do p vodn ho potrub namontovat red...

Страница 18: ...h m rs klete Melegv z csatlakoz s W H balra Hidegv z csatlakoz s K C jobbra Minim lis t raml mennyis g 5 l perc Az 5 bar nagys got t ll p tfoly si nyom s eset ben javasolt nyom scs kkent beszerel se...

Страница 19: ...W H esquerda Liga o de gua fria K C direita Caudal m nimo 5 l min Em caso de press o de caudal acima de 5 bar recomenda se montar um redutor de press o na tubagem de alimenta o Aten o ao perigo de con...

Страница 20: ...ant s K C sa Minimum debi 5 l dak 5 bar n zerindeki ak bas nc nda besleme hatt na bir bas n d r c n n monte edilmesi onar l r Don tehlikesine dikkat Binan n su tesisat n bo altma esnas nda termostatla...

Страница 21: ...18 RUS 3 34 953 1 2 a b 34 954 2 0 5 1 10 1 5 16 3 34 953 37 5 34 954 24 80 C 60 C 38 C 2 C W H 5 5 3 y z 4 5 4 6 W H...

Страница 22: ...o 2 C vy ia ako teplota zmie anej vody Pr pojka teplej vody W H v avo Pr pojka studenej vody K C vpravo Minim lny prietok 5 l min Pri statick ch tlakoch vy ch ne 5 barov sa mus do pr vodn ho potrubia...

Страница 23: ...temperature me ane vode Priklju ek tople vode W H levo Priklju ek hladne vode K C desno Najmanj i pretok 5 l min Kadar preto ni tlak presega 5 bar se priporo a da se v napajalne vode vgradi reducirni...

Страница 24: ...ak tople vode W H lijevo Priklju ak hladne vode K C desno Minimalni protok 5 l min Ako je hidrauli ki tlak ve i od 5 bar preporu uje se da se na opskrbni vod ugradi reduktor tlaka Sprje avanje teta o...

Страница 25: ...22 BG 3 34 953 A 1 2 a b c 34 954 2 0 5 1 10 1 5 16 3 34 953 37 5 34 954 24 80 C 60 C 38 C 2 C W H K C 5 5 3 x y z 4 5 B 4 6 W H K C...

Страница 26: ...peratuur Kuumavee hendus W H vasakul K lmavee hendus K C paremal Minimaalne l bivool 5 l min Kui segisti veesurve on le 5 baari soovitatakse veetorudesse paigaldada survealandusventiil Ettevaatust k l...

Страница 27: ...ajaukt dens temperat ru Karst dens piesl gums W H Pa kreisi Aukst dens piesl gums K C Pa labi Maz k caurlaides sp ja 5 l min Ja hidrauliskais spiediens p rsniedz 5 bar ieteicams ieb v t padeves vad b...

Страница 28: ...ens temperat ra ma iausiai 2 C auk tesn u sumai yto vandens temperat r Kar to vandens jungtis W H kair je alto vandens jungtis K C de in je Ma iausias debitas 5 l min Jeigu vandens sl gis didesnis nei...

Страница 29: ...dicat dec t temperatura pentru apa de amestec Racord de ap cald W H st nga Racord de ap rece K C dreapta Debitul minim 5 l min La presiuni de curgere mai mari de 5 bar se recomand instalarea unui redu...

Страница 30: ......

Отзывы: