4) Fault:
The operating mode of the heater cannot be controlled during wind /heater firing/
low chimney draft during operation. Smoke partly escapes through the firebox door. Smoke
enters the sauna.
Possible cause:
• Blockage in the chimney or flue channels of the heater.
• The chimney height is not sufficient or the chimney is located next to a high obstacle.
• There is cold air in the chimney; the chimney has not heated up.
• Low quality or wet combustion material.
• The chimney is installed incorrectly.
Troubleshooting methods:
• Perform maintenance (paragraph 2.8).
• Extend the chimney stack height.
• Insulate the chimney stack with a non-combustible heat-insulation material.
• Select a heat-insulated chimney stack.
• Remove ash from the ash drawer.
• Check combustion material for compliance with the requirements (paragraph 2.4).
• Ensure supply of a sufficient volume of combustion air.
• Check the correctness of chimney installation and/or compliance with the
manufacturer’s requirements; trust the installation and disassembly of the chimney
only to qualified specialists.
3. INSTALLATION MANUAL
3.1. Before commencing installation of the heater
IMPORTANT! Make sure that all safety distances around the heater are observed. There
shall be no electrical appliances, cables, meltable and flammable materials within the
safety distances. Consider the safety distances from the chimney during installation!
• The heater shall be installed in compliance with all local rules, including those referring to
European and national standards.
• The chimney stack for the heater shall be individual, not joint combined for several
appliances.
• For more information about fire safety requirements, please, address the local fire
department.
• Check the availability of all the heater component parts. Make sure that all the heater
bolted connections are tightened.
3.1.1. Configuration of sauna ventilation
1) Self-ventilation (Figure 1):
Air inlet (A)
shall be located close to the floor next to the heater. Air inlet is necessary for
fresh air supply to the sauna.
Exhaust outlet (B)
shall be located under the ceiling as far as possible from the heater.
The primary purpose of exhaust outlet is to remove moisture from the sauna after steam
bathing.
2) Mechanical exhaust ventilation (Figure 2):
Air inlet (A)
shall be located at the height of about 500 mm over the stone heater.
Exhaust outlet (B)
shall be located as close as possible to the floor, for example, under a
bench.