Press <SAVE> to exit the menu and return to normal operation or <MENU> to 

repeat the menu.

28. EXIT

CALIBRATION

The CO transmitter features a cover mounted 

sensor PCB that is pre-calibrated. This means 

that the entire sensor PCB can simply be 

replaced with a new calibrated PCB if desired 

without having to remove the enclosure and 

the main processor board. This sensor swap 

can be completed in seconds. Simply unplug 

the device ribbon cable connection, remove 

the old sensor PCB, install the new PCB and 

reconnect the ribbon cable. There is no need 

to make any adjustments or apply gas to the 

transmitter using the sensor swap method. 

In 

this case, the Fault Mode should be reset if it 

is enabled.

The device may also be calibrated or verified with the CO gas if required. This requires a field calibration kit 

consisting of a bottle of gas (250 ppm CO in air for example), a tank pressure regulator with flow restrictor 

and the necessary tubing with a calibration cap to cover to the sensor. Calibration can be done at 20 to 

27°C.

Verification with gas can be done without removing the device cover. Simply apply gas using the calibration 

cap attached directly to the port on the cover and monitor the output signal or LCD.

The device cover must be opened to perform an actual calibration. In the case, the gas calibration cap 

attached to the sensor fixture on the cover as before. The sensor must be continuously powered for at least 

1/2 hour prior to calibration. Calibrate the sensor first in clean air with no CO gas present. Simply adjust the 

ZERO pot on the sensor board until 4 mA (or 0 Vdc) output is obtained and the LCD displays 0 ppm. Note 

that the "0 Filter" menu item should be disabled to set the 0 ppm. The ZERO and SPAN pots are located on 

the edge of the cover sensor PCB and are clearly marked on the PCB.

Then attach the gas supply. Turn the regulator on/off knob fully off and attach it to the 250 ppm gas bottle 

and firmly tighten it by hand. Moisten the sponge and squeeze out any excess water. Place the sponge in 

the cap so that it will not touch the sensor but does not plug the hole in the side of the cap. Attach the cap 

to the fixture over the sensor. If the gas cap is too loose on the fixtures, simply place a wrap of electrical 

tape around the cap the tighten. Slowly turn the valve knob on the regulator to let the gas begin flowing.

The regulator will restrict the flow rate to the specified 200 ml/min and the sponge will ensure the gas is 

in the right humidity range. Wait for 5 minutes and then adjust the SPAN pot on the sensor board until the 

output and LCD reads 250 ppm. Close the valve on the tank and take a cap off from the sensor. 

Calibration 

is complete. In this case, the ReCal Mode should be reset if it is enabled.

DIMENSIONS

Figure 5

IN-GE-CMD5B5XXX-01-02     03/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание CMD5B5 Series

Страница 1: ...ve feet from corners and other items that may cause disturbances in the air flow Avoid areas with vibrations or rapid temperature changes The duct CO detector principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the probe into the enclosure over the CO sensor and then is drawn ba...

Страница 2: ...power is applied The current signal has a maximum load that it will drive and the voltage output has a minimum load Follow the ratings in the Specification section or inaccurate readings may result The power must be disconnected to change from VOLT to mA The analog output CO signal is typically connected directly to the Building Automation System BAS and used as a control parameter or for logging ...

Страница 3: ...eset to Normal Mode when the CO level drops below the trip level hysteresis value In order to reset the relay alarms to Normal Mode the user must also press theTEST switch on the front cover or activate the remote TEST input If the CO level is below the alarm level AND the TEST switch is pressed then the relay alarms will return to the Normal Mode The Manual Reset also applies to the buzzer alarm ...

Страница 4: ... device network address the installer MUST change the settings before operation Any changes made are saved in non volatile memory and are restored in case of a power loss Only the menu items relevant to the device model will be shown The menu can be accessed at any time after the warm up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue Note that t...

Страница 5: ...used for Fail Safe operation as the relay will change state on power loss Press SAVE to save the setting Use the ROLL key to toggle relay 1 ON or OFF MENU Press to advance to next menu item MENU Press to advance to next menu item MENU Press to advance to next menu item 7 HYSTERESIS 8 DELAY 9 DIRECT 10 TEST Only if Relay 1 installed MENU Press to advance to next menu item Only if Relay 2 installed ...

Страница 6: ...when the TEST switch is pressed Use the ROLL key to enable disable or reset When disabled the device will not sound the buzzer or provide LCD and status LED indication when the sensor life is exceeded When enabled the fault alarm will activate to indicate the sensor life is exceeded Press SAVE to save the setting If it is set to reset and SAVE is pressed then the fault condition is cleared the lif...

Страница 7: ...he setting to either CO Value or Status When set to CO value the actual ppm value of the CO reading will be displayed on the LCD When set to Status the ppm value will not be displayed only the device operating status Press SAVE to save the setting Use the ROLL key to enable or disable the LCD backlight When enabled the backlight is always on and when disabled it never lights Press SAVE to save the...

Страница 8: ... on the cover as before The sensor must be continuously powered for at least 1 2 hour prior to calibration Calibrate the sensor first in clean air with no CO gas present Simply adjust the ZERO pot on the sensor board until 4 mA or 0 Vdc output is obtained and the LCD displays 0 ppm Note that the 0 Filter menu item should be disabled to set the 0 ppm The ZERO and SPAN pots are located on the edge o...

Страница 9: ...1 minute increments OPTIONAL RELAY Outputs Form C contacts NO and NC 5 Amps 250 Vac 5 Amps 30 Vdc Relay 1 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay 2 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay Hysteresis Programmable 10 to 100 ppm in 5 ppm increments Relay Delay Programmable 0 to 10 minutes in 1 minute increments GENERAL Measurement Electrochemical Samp...

Отзывы: