Page 5
Relay 1
Trip 50
Use the <ROLL> key to scroll through the available options. The
relay 1 alarm trip point may be set from 20 to 500 ppm in 10
ppm increments. Press <SAVE> to save the setting.
<MENU>
Press to advance to next menu item
6. ALARM TRIP
POINT
Relay 1
Hyst 10
Relay 1
Del 2Min
Relay 1
Direct
Relay 1
Test OFF
Use the <ROLL> key to scroll through the available options.
The relay 1 hysteresis may be set from 10 to 100 ppm in 5
ppm increments. Press <SAVE> to save the setting. Note that
the maximum value may be limited by the trip point value.
Use the <ROLL> key to scroll through the available options.
The relay 1 delay may be set from 0 to 10 minutes in 1 minute
increments. Press <SAVE> to save the setting.
Use the <ROLL> key to toggle the available options. Relay 1
operation may be set to Direct or Reverse. Direct operation
means the relay is normally not energized and will energize
on an alarm condition (the NO/NC PCB destinations are
correct). Reverse operation means the relay is normally
energized and ill de-energize on an alarm condition (the NO/
NC PCB designations are reversed). Reverse operation can be
used for "Fail Safe" operation as the relay will change state on
power loss. Press <SAVE> to save the setting.
Use the <ROLL> key to toggle relay 1 ON or OFF.
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
7. HYSTERESIS
8. DELAY
9. DIRECT
10. TEST
Only if
Relay 1
installed
<MENU>
Press to advance to next menu item
Only if
Relay 2
installed
Relay 2
Hyst 20
Relay 2
Del 2Min
Use the <ROLL> key to scroll through the available options.
The relay 2 hysteresis may be set from 10 to 100 ppm in 5 ppm
increments. Press <SAVE> to save the setting. Note that the
maximum value may be limited by the trip point value.
Use the <ROLL> key to scroll through the available options.
The relay 2 delay may be set from 0 to 10 minutes in 1 minute
increments. Press <SAVE> to save the setting.
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
12. HYSTERESIS
13. DELAY
Relay 2
Trip 150
Use the <ROLL> key to scroll through the available options.
The relay 2 alarm trip point may be set from 20 to 500 ppm in
10 ppm increments. Press <SAVE> to save the setting.
<MENU>
Press to advance to next menu item
11. ALARM TRIP
POINT