SPECIFICATIONS

POWER SUPPLY

Power Supply .......................24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified)

Consumption .......................100 mA max (with all options on)

Protection Circuitry ............Reverse voltage protected, output limited and transient protected

Ouput Signal ........................4-20 mA active, 0-5 or 0-10 Vdc (selectable)

Output Drive Capability ...

Current:

 450 Ω max

 

Voltage:

 10K Ω min

ENCLOSURE

LCD Display ...........................1 ppm resolution, 35mm W x 15mm H, alpha-numeric

 

(1.4" x 0.6") with backlight

Status LED .............................Two color (red/green) on front panel

Test Switch ............................Performs I/O tests, front panel and remote connection

Dimensions ...........................127mm W x 101mm H x 65mm D (5" x 4" x 2.55")

Agency Approvals ..............Sensor is UL recognized for ANSI/UL-2034 and UL-2075, E240671

BUZZER

Alarm.......................................85db @ 10 cm

Trip Point ...............................Programmable 20 to 500 ppm in 10 ppm increments

Delay .......................................Programmable 0 to 10 minutes in 1 minute increments

OPTIONAL RELAY

Outputs ..................................Form C contacts (NO and NC), 5 Amps @ 250 Vac, 5 Amps @ 30 Vdc

Relay 1 Trip Point ................Programmable 20 to 500 ppm in 10 ppm increments

Relay 2 Trip Point ................Programmable 20 to 500 ppm in 10 ppm increments

Relay Hysteresis...................Programmable 10 to 100 ppm in 5 ppm increments

Relay Delay ...........................Programmable 0 to 10 minutes in 1 minute increments

GENERAL

Measurement .......................Electrochemical

Sample Method ..................Diffusion

Measurement Range .........0-100, 150, 300, 400 or 500 ppm (selectable)

Accuracy ................................±5 ppm or ±5% of reading (whichever is greater)

 

0 to 50°C (32 to 122°F), 15 to 90 %RH

Operating Conditions .......-20 to 50°C (-4 to 122°F), 15 to 90 %RH, 0.9 to 1.1 atm

Stability ..................................<5% signal loss/year

Response Time ....................<60 seconds for 90% step change

Enclosure ...............................127 mm W x 101 mm H x 65 mm D (5.0" x 4.0" x 2.55")

Duct Probe ............................177 mm (7") long x 25.4 mm (1") diameter

Wiring Connections ...........Screw terminal block (14 to 22 AWG)

Country of Origin ................. Canada

IN-GE-CMD5B5XXX-01-02     03/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание CMD5B5 Series

Страница 1: ...ve feet from corners and other items that may cause disturbances in the air flow Avoid areas with vibrations or rapid temperature changes The duct CO detector principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the probe into the enclosure over the CO sensor and then is drawn ba...

Страница 2: ...power is applied The current signal has a maximum load that it will drive and the voltage output has a minimum load Follow the ratings in the Specification section or inaccurate readings may result The power must be disconnected to change from VOLT to mA The analog output CO signal is typically connected directly to the Building Automation System BAS and used as a control parameter or for logging ...

Страница 3: ...eset to Normal Mode when the CO level drops below the trip level hysteresis value In order to reset the relay alarms to Normal Mode the user must also press theTEST switch on the front cover or activate the remote TEST input If the CO level is below the alarm level AND the TEST switch is pressed then the relay alarms will return to the Normal Mode The Manual Reset also applies to the buzzer alarm ...

Страница 4: ... device network address the installer MUST change the settings before operation Any changes made are saved in non volatile memory and are restored in case of a power loss Only the menu items relevant to the device model will be shown The menu can be accessed at any time after the warm up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue Note that t...

Страница 5: ...used for Fail Safe operation as the relay will change state on power loss Press SAVE to save the setting Use the ROLL key to toggle relay 1 ON or OFF MENU Press to advance to next menu item MENU Press to advance to next menu item MENU Press to advance to next menu item 7 HYSTERESIS 8 DELAY 9 DIRECT 10 TEST Only if Relay 1 installed MENU Press to advance to next menu item Only if Relay 2 installed ...

Страница 6: ...when the TEST switch is pressed Use the ROLL key to enable disable or reset When disabled the device will not sound the buzzer or provide LCD and status LED indication when the sensor life is exceeded When enabled the fault alarm will activate to indicate the sensor life is exceeded Press SAVE to save the setting If it is set to reset and SAVE is pressed then the fault condition is cleared the lif...

Страница 7: ...he setting to either CO Value or Status When set to CO value the actual ppm value of the CO reading will be displayed on the LCD When set to Status the ppm value will not be displayed only the device operating status Press SAVE to save the setting Use the ROLL key to enable or disable the LCD backlight When enabled the backlight is always on and when disabled it never lights Press SAVE to save the...

Страница 8: ... on the cover as before The sensor must be continuously powered for at least 1 2 hour prior to calibration Calibrate the sensor first in clean air with no CO gas present Simply adjust the ZERO pot on the sensor board until 4 mA or 0 Vdc output is obtained and the LCD displays 0 ppm Note that the 0 Filter menu item should be disabled to set the 0 ppm The ZERO and SPAN pots are located on the edge o...

Страница 9: ...1 minute increments OPTIONAL RELAY Outputs Form C contacts NO and NC 5 Amps 250 Vac 5 Amps 30 Vdc Relay 1 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay 2 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay Hysteresis Programmable 10 to 100 ppm in 5 ppm increments Relay Delay Programmable 0 to 10 minutes in 1 minute increments GENERAL Measurement Electrochemical Samp...

Отзывы: