background image

Page  3

OPERATION - START UP

The device will initially start up in warm-up mode which lasts for about two minutes. Immediately after 

applying power the LCD will display the software version number and begin a two minute countdown.

During the warm-up mode the alarm relays will be set to off, the LED will flash red, all communications are 

disabled, the key pad is disabled and the analog output will be set to it's minimum value.

OPERATION - NORMAL MODE

In normal operation the sensor will measure the CO level in the duct air and output a proportional value 

on the analog output which is scaled to the default range of 0-300 ppm. The CO reading will also be 

displayed on the LCD and updated in the communication value. If alarm relays are installed, the present 

CO reading is compared to the setpoints and appropriate action is taken if an alarm condition exists. The 

status LED on the front cover will be green to indicate normal operation.

OPERATION - ALARM MODE

The CO reading is compared to pre-set setpoints for alarms and if they are exceeded the device enters 

Alarm mode. The alarm reset back to Normal mode can be configured via the menu as either Automatic 

Reset or Manual Reset.

Automatic Alarm Reset (Default)

Two optional relays are used to indicate alarm conditions. The trip point, hysteresis and delay time of 

each relay can be programmed via the menu. For example, Relay 1 defaults to a 50 ppm trip point, 10 

ppm hysteresis and 2 minute delay time. Relay 2 defaults to a 150 ppm trip point, 20 ppm hysteresis and 

2 minute delay time  All of these values can be changed via the menu. In the example for Relay 1, a timer 

is started when the CO level exceeds 50 ppm (the trip level). If the level drops below 50 ppm before 2 

minutes (the delay time) has expired then the relay is not activated. If the CO level exceeds 50 ppm for 

2 minutes then the relay is activated. The relay will remain activated until the CO level drops below 40 

ppm (trip level – hysteresis). This relay can be used to signal a “low alarm”. Relay 2 operates in the same 

manner and has independently programmable trip point, hysteresis and delay time. This relay can be used 

to signal a “high alarm”. The LCD will indicate the Alarm mode details and the LED will flash red.

Manual Alarm Reset

In this case, the alarm relays will activate the same way as described above but will not automatically reset 

to Normal Mode when the CO level drops below the trip level - hysteresis value. In order to reset the relay 

alarms to Normal Mode the user must also press the TEST switch on the front cover (or activate the remote 

TEST input). If the CO level is below the alarm level AND the TEST switch is pressed, then the relay alarms 

will return to the Normal Mode.

The Manual Reset also applies to the buzzer alarm. If the buzzer alarm is active, pressing the TEST switch 

will "silence" the buzzer. If the buzzer alarm was active but the CO level has been reduced below the trip 

point, then the TEST switch must be pressed to reset the buzzer alarm to the Normal Mode.

OPERATION - TEST MODE

The Test mode function is disabled by default, it must be enabled via the menu to operate. To initiate the 

Test function during normal operation, either press and hold the TEST switch for 1 second or activate it 

remotely by shorting the TEST + to TEST – (COM). This will cause the Status LED to blink red, the analog 

output to go to 100% and both relays to activate. The buzzer will also beep once every 15 seconds if 

enabled and the LCD will indicate the Test mode and the remaining time. The Test function will continue for 

5 minutes (default) and then the device will reset to normal operation. The Test function can be cancelled 

by pressing the TEST switch a second time. Test mode cannot be activated if the device is in Fault, Alarm or 

Re-Cal modes of operation, only in Normal mode. The Test function is useful to verify the output and alarm 

relay operation and the Test time can be programmed via the menu.

OPERATION - FAULT MODE

The Fault mode function is disabled by default, it must be enabled via the menu to operate. The Fault 

function will monitor the CO sensor lifetime and indicate when the CO sensor should be replaced. If the 

device determines that the sensor has reached the end of it's useful life and that replacement is necessary 

it will enter Fault mode. This will cause the Status LED to blink red and the buzzer to beep once every 10 

minutes. The LCD will periodically show "Sensor Fault". The Fault mode can be disabled via the menu or 

enabled at any time. If enabled, and the device is in Fault mode, pressing the TEST switch will "silence" the 

buzzer due to the Fault alarm only. Buzzer silence due to the Fault alarm will hold until the Fault condition 

is reset via the menu. The buzzer may still activate due to a CO setpoint alarm if enabled.

IN-GE-CMD5B5XXX-01-02     03/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание CMD5B5 Series

Страница 1: ...ve feet from corners and other items that may cause disturbances in the air flow Avoid areas with vibrations or rapid temperature changes The duct CO detector principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the probe into the enclosure over the CO sensor and then is drawn ba...

Страница 2: ...power is applied The current signal has a maximum load that it will drive and the voltage output has a minimum load Follow the ratings in the Specification section or inaccurate readings may result The power must be disconnected to change from VOLT to mA The analog output CO signal is typically connected directly to the Building Automation System BAS and used as a control parameter or for logging ...

Страница 3: ...eset to Normal Mode when the CO level drops below the trip level hysteresis value In order to reset the relay alarms to Normal Mode the user must also press theTEST switch on the front cover or activate the remote TEST input If the CO level is below the alarm level AND the TEST switch is pressed then the relay alarms will return to the Normal Mode The Manual Reset also applies to the buzzer alarm ...

Страница 4: ... device network address the installer MUST change the settings before operation Any changes made are saved in non volatile memory and are restored in case of a power loss Only the menu items relevant to the device model will be shown The menu can be accessed at any time after the warm up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue Note that t...

Страница 5: ...used for Fail Safe operation as the relay will change state on power loss Press SAVE to save the setting Use the ROLL key to toggle relay 1 ON or OFF MENU Press to advance to next menu item MENU Press to advance to next menu item MENU Press to advance to next menu item 7 HYSTERESIS 8 DELAY 9 DIRECT 10 TEST Only if Relay 1 installed MENU Press to advance to next menu item Only if Relay 2 installed ...

Страница 6: ...when the TEST switch is pressed Use the ROLL key to enable disable or reset When disabled the device will not sound the buzzer or provide LCD and status LED indication when the sensor life is exceeded When enabled the fault alarm will activate to indicate the sensor life is exceeded Press SAVE to save the setting If it is set to reset and SAVE is pressed then the fault condition is cleared the lif...

Страница 7: ...he setting to either CO Value or Status When set to CO value the actual ppm value of the CO reading will be displayed on the LCD When set to Status the ppm value will not be displayed only the device operating status Press SAVE to save the setting Use the ROLL key to enable or disable the LCD backlight When enabled the backlight is always on and when disabled it never lights Press SAVE to save the...

Страница 8: ... on the cover as before The sensor must be continuously powered for at least 1 2 hour prior to calibration Calibrate the sensor first in clean air with no CO gas present Simply adjust the ZERO pot on the sensor board until 4 mA or 0 Vdc output is obtained and the LCD displays 0 ppm Note that the 0 Filter menu item should be disabled to set the 0 ppm The ZERO and SPAN pots are located on the edge o...

Страница 9: ...1 minute increments OPTIONAL RELAY Outputs Form C contacts NO and NC 5 Amps 250 Vac 5 Amps 30 Vdc Relay 1 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay 2 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay Hysteresis Programmable 10 to 100 ppm in 5 ppm increments Relay Delay Programmable 0 to 10 minutes in 1 minute increments GENERAL Measurement Electrochemical Samp...

Отзывы: