Page 15
SLT 5.0 Level and Flow Monitor
RELAY PARAMETERS
Relay
Press
and
or
to select a corresponding relay number (2
relays are standard, 4 additional are optional).
Function
Press
or
to select
Off
,
Temperature
,
Pulse
and
Level
.
Temperature
References temperature reading from the
SLT 5.0 ultrasonic sensor (air temperature
at the sensor location). Press
and
and
set the relay On and Off set points.
Pulse
Press
and set digits to the flow volume
increment required between relay pulses.
Use this feature for remote samplers,
chlorinators or totalizers. Minimum time
between pulses is 2.25 seconds and pulse
duration is 350 milliseconds.
Level
Press
to
Mode
and
to select
Pump
,
Low Alarm
or
Hi Alarm
.
Note:
Function
setting
Level
will change according to selections made under
Units/Mode
eg
Level
,
Range
,
Flow
,
Volume
or
HRT
.
Press
to return to
Menu Selections
.
DATA LOGGING (OPTIONAL)
Refer to Options section of this manual.