background image

17

Model MSCF Modular Small Cabinet Fan

®

Coil Maintenance

Start-Up Documentation

CAUTION

Fin edges are sharp.

Coils must be clean to obtain maximum performance. 
Check once a year under normal operating conditions 
and, if dirty, brush or vacuum clean. Soiled fins reduce 
the capacity of the coil, demand more energy from the 
fan, and create an environment for odor and bacteria 
to grow and spread through the conditioned zone. 
High pressure water (400 psi or less) may be used to 
clean coils with fin thickness over 0.006 inches thick. 

Test the spray pressure

 over a small corner of the 

coil to determine if the fins will withstand the spray 
pressure.
For coils with fragile fins or high fin density, foaming 
chemical sprays and washes are available. Many coil 
cleaners contain harsh chemicals, so they must be 
used with caution by qualified personnel only. Care 
must be taken not to damage the coils, including fins, 
while cleaning.

Winterizing Coils

Coil freeze-up can be caused by such things as air 
stratification and failure of outdoor air dampers and/
or preheat coils. Routine draining of water cooling 
coils for winter shutdown cannot be depended upon 
as insurance against freeze-up. Severe coil damage 
may result. It is recommended that all coils be drained 
as thoroughly as possible and then treated in the 
following manner.
Fill each coil independently with an antifreeze solution 
using a small circulating pump and again thoroughly 
drain. Check freezing point of antifreeze before 
proceeding to next coil. Due to a small amount of 
water always remaining in each coil, there will be 
diluting effect. The small amount of antifreeze solution 
remaining in the coil must always be concentrated 
enough to prevent freeze-up.
NOTE: Carefully read instructions for mixing antifreeze 
solution used. Some products will have a higher 
freezing point in their natural state than when mixed 
with water.

Job Information

Job Name 

  _________________________________

Address 

  _________________________________

City  ________________  State  ______  Zip  ___________
Phone Number    _________________________________ 
Contact Person    _________________________________ 

Start-Up Company Information

Service Oranization  _______________________________
Address 

 _______________________________

City  ________________  State  ______  Zip  ___________
Phone Number 

 _______________________________

Fax Number 

 _______________________________

Start-Up Date 

 _______________________________

Start-Up Personnel Name __________________________

Nameplate Information

Unit Model Number  _______________________________
Volts ________________ Hertz  ________ Phase   _______
Amps _______________Mark   _______________________
Fan rpm _____________
Unit Serial Number   _______________________________

Field Start-Up Documentation

 

Check blower rotation

 

Check air volume (cfm)

 

 _________ Design

 

 _________ Actual

 

Actual motor voltage 

  _________   Volts

 

Actual motor hertz 

  _________   Hertz

 

Actual motor phase 

  _________   Phase

 

Actual motor amps 

  _________   Amps

Drive
 

Fan RPM Range

 

 _________ Minimum

 

 _________ Maximum

Drain Pan Maintenance

Drain pans in any air conditioning unit will have 
some moisture in them, therefore, algae and other 
organisms will grow due to airborne spores and 
bacteria. Periodic cleaning is necessary to prevent 
this buildup from plugging the drain and causing the 
drain pan to overflow. Inspect twice a year to avoid 
the possibility of overflow. Also, drain pans should be 
kept clean to prevent the spread of disease. Cleaning 
should be performed by qualified personnel.

Содержание MSCF-BI

Страница 1: ...ation and Maintenance Manual Please read and save these instructions Read carefully before attempting to assemble install operate or maintain the product described Protect yourself and others by obser...

Страница 2: ...are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The c...

Страница 3: ...Electric Heater 15 Maintenance Fan 16 Coil 16 Drain Pan 16 Reference Start Up Documentation 17 Maintenance Log 18 19 Warranty Backcover Unit Layout 1 Fan and Cabinet Section 2 Cooling Section Chilled...

Страница 4: ...3 0 inch 3 8 16 Spinlock Nut Two required per assembly 3 8 16 Spinlock Nut Two required per assembly HANGING ASSEMBLY BASE ASSEMBLY Mounting Instructions Greenheck s Modular Small Cabinet Fan MSCF sho...

Страница 5: ...4 Row HW Steam 15 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 20 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 25 6 75 21 18 5 6 75 6 75 21 6 75 9 5 18 5 23 38 2 5 3 5...

Страница 6: ...ertical Quantity Face Area Sloped Quantity Face Area 15 9x18 2 1 8 12x12 1 2 5 12x24 1 20 12x12 1 2 5 16x16 1 3 4 12x24 1 16x20 1 25 14x18 2 3 0 16x20 2 3 8 30 16x16 1 3 4 12x24 1 5 3 16x20 1 24x24 1...

Страница 7: ...15 50 9 38 3 188 1 375 4 0 26 0 85 8 6 62 12 75 9 38 3 188 1 375 4 0 26 0 All dimensions are in inches NOTE With airflow from left to right the fluid enters the coil from the bottom connection Inlet...

Страница 8: ...2 50 24 5 21 0 10 12 14 1 38 1 63 65 6 7 50 24 5 26 0 10 12 14 1 38 1 63 85 8 6 62 24 5 26 0 10 12 14 1 38 1 63 All dimensions are in inches Unit Size Face Area A B C L M N P 4 Row 6 Row 8 Row All Al...

Страница 9: ...should be capped off cap Unit Size Face Area A B C D E F G 4 Row 6 8 Row 4 Row 6 Row 8 Row 30 3 2 38 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 0 45 4 5 50 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 5 5...

Страница 10: ...rage and Fan RPM All access doors must be installed Measure and record the input voltage and motor amperage s To measure the fan RPM the blower door will need to be removed Minimize measurement time b...

Страница 11: ...ductwork Repair Elbows or other obstructions may restrict fan outlet Correct or improve ductwork Belt slippage Adjust belt tension Unit running backwards Correct as shown in System Start Up section S...

Страница 12: ...independently of the coils Undue stress should not be applied at the connection to coil headers 2 The condensate drain pipe should be sized adequately to ensure the condensate drains properly See Drai...

Страница 13: ...are recommended for low pressure steam On high pressure systems bucket traps are normally recommended The thermostatic traps should be used only for air venting 3 Bucket traps are recommended for use...

Страница 14: ...he requirements and practices described below are based on the National Electric Code NEC and The Space Heating Standard of the Underwriters Laboratories Inc UL Although UL requirements are uniform th...

Страница 15: ...with the thermostat set to 70 F the heater will be off with a temperature sensing above 70 F As the temperature varies the steps turn on and off to hold the setpoint discharge temperature The colder...

Страница 16: ...n air Occasionally oil and dust may accumulate on the wheel causing imbalance When this occurs the wheel and housing should be cleaned to assure smooth and safe operation Inspect fan impeller and hous...

Страница 17: ...rated enough to prevent freeze up NOTE Carefully read instructions for mixing antifreeze solution used Some products will have a higher freezing point in their natural state than when mixed with water...

Страница 18: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Страница 19: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Страница 20: ...or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo g...

Отзывы: