Model MSCF Modular Small Cabinet Fan

®

2P = minimum

2P = minimum

Drain Pan / Drain Trap

Drain Pan / Drain Trap

Drain lines and traps should be run full size from the 
drain pan connection. Drain pans should have drain 
lines and traps to permit the condensate from the 
coils to drain freely. On all units with drain pans, the 
trap depth and the distance between the trap outlet 
and the drain pan outlet should be twice the static 
pressure (P) in the drain pan section under normal 
operation to assure the trap remains sealed.

General - 

continued

5.  It is recommended that vacuum breakers be 

installed on all applications to prevent retaining 
condensate in the coil. Generally, the vacuum 
breaker is to be connected between the coil inlet 
and the return main. The vacuum breaker should 
be open to the atmosphere and the trap design 
should allow venting of large quantities of air.

6.  Do not attempt to lift condensate when using 

modulating or on-off control.

7.  Do not reduce the pipe size leaving the coil.

Traps

1.  Size traps in accordance with the manufacturer’s 

recommendations. Be certain that the required 
pressure differential will always be available. DO 
NOT UNDERSIZE.

2.  Float and thermostatic or bucket traps are 

recommended for low pressure steam. On high 
pressure systems, bucket traps are normally 
recommended. The thermostatic traps should be 
used only for air venting.

3.  Bucket traps are recommended for use with on-off 

control only.

4.  Locate traps at least 12 inches below the coil 

return connection.

Controls

1.  On high pressure installations, a two-position 

steam valve with a face and bypass arrangement is 
preferred where modulating control is required.

2.  Modulating valves must be sized properly. DO NOT 

UNDERSIZE.

Freezing Conditions (entering air below 35°F)

1.  5 PSI steam must be supplied to the coil at all times.
2.  Modulating valves are not recommended. Control 

should be by means of face and bypass dampers.

3.  Provision should always be made to thoroughly 

mix fresh air and return air before it enters the 
coil on return air units. Also, temperature control 
elements must be properly located to obtain true 
air mixture temperatures.

4.  As additional protection against freeze-up, the trap 

should be installed sufficiently —far below the coil 
to provide an adequate hydrostatic head to ensure 
removal of condensate during an interruption in the 
steam pressure. Estimate 3 feet for each 1 PSI of 
trap differential required.

5.  On start-up, admit steam to coil ten minutes before 

admitting outdoor air.

6.  Provision must be made to close fresh air dampers 

if steam supply pressure falls below minimum 
specified.

Содержание MSCF-BI

Страница 1: ...ation and Maintenance Manual Please read and save these instructions Read carefully before attempting to assemble install operate or maintain the product described Protect yourself and others by obser...

Страница 2: ...are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The c...

Страница 3: ...Electric Heater 15 Maintenance Fan 16 Coil 16 Drain Pan 16 Reference Start Up Documentation 17 Maintenance Log 18 19 Warranty Backcover Unit Layout 1 Fan and Cabinet Section 2 Cooling Section Chilled...

Страница 4: ...3 0 inch 3 8 16 Spinlock Nut Two required per assembly 3 8 16 Spinlock Nut Two required per assembly HANGING ASSEMBLY BASE ASSEMBLY Mounting Instructions Greenheck s Modular Small Cabinet Fan MSCF sho...

Страница 5: ...4 Row HW Steam 15 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 20 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 25 6 75 21 18 5 6 75 6 75 21 6 75 9 5 18 5 23 38 2 5 3 5...

Страница 6: ...ertical Quantity Face Area Sloped Quantity Face Area 15 9x18 2 1 8 12x12 1 2 5 12x24 1 20 12x12 1 2 5 16x16 1 3 4 12x24 1 16x20 1 25 14x18 2 3 0 16x20 2 3 8 30 16x16 1 3 4 12x24 1 5 3 16x20 1 24x24 1...

Страница 7: ...15 50 9 38 3 188 1 375 4 0 26 0 85 8 6 62 12 75 9 38 3 188 1 375 4 0 26 0 All dimensions are in inches NOTE With airflow from left to right the fluid enters the coil from the bottom connection Inlet...

Страница 8: ...2 50 24 5 21 0 10 12 14 1 38 1 63 65 6 7 50 24 5 26 0 10 12 14 1 38 1 63 85 8 6 62 24 5 26 0 10 12 14 1 38 1 63 All dimensions are in inches Unit Size Face Area A B C L M N P 4 Row 6 Row 8 Row All Al...

Страница 9: ...should be capped off cap Unit Size Face Area A B C D E F G 4 Row 6 8 Row 4 Row 6 Row 8 Row 30 3 2 38 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 0 45 4 5 50 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 5 5...

Страница 10: ...rage and Fan RPM All access doors must be installed Measure and record the input voltage and motor amperage s To measure the fan RPM the blower door will need to be removed Minimize measurement time b...

Страница 11: ...ductwork Repair Elbows or other obstructions may restrict fan outlet Correct or improve ductwork Belt slippage Adjust belt tension Unit running backwards Correct as shown in System Start Up section S...

Страница 12: ...independently of the coils Undue stress should not be applied at the connection to coil headers 2 The condensate drain pipe should be sized adequately to ensure the condensate drains properly See Drai...

Страница 13: ...are recommended for low pressure steam On high pressure systems bucket traps are normally recommended The thermostatic traps should be used only for air venting 3 Bucket traps are recommended for use...

Страница 14: ...he requirements and practices described below are based on the National Electric Code NEC and The Space Heating Standard of the Underwriters Laboratories Inc UL Although UL requirements are uniform th...

Страница 15: ...with the thermostat set to 70 F the heater will be off with a temperature sensing above 70 F As the temperature varies the steps turn on and off to hold the setpoint discharge temperature The colder...

Страница 16: ...n air Occasionally oil and dust may accumulate on the wheel causing imbalance When this occurs the wheel and housing should be cleaned to assure smooth and safe operation Inspect fan impeller and hous...

Страница 17: ...rated enough to prevent freeze up NOTE Carefully read instructions for mixing antifreeze solution used Some products will have a higher freezing point in their natural state than when mixed with water...

Страница 18: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Страница 19: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Страница 20: ...or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo g...

Отзывы: