Greenheck MSCF-BI Скачать руководство пользователя страница 11

11

Model MSCF Modular Small Cabinet Fan

®

Symptom

Possible Cause

Corrective Action

Blower fails to 

operate

Blown fuse or open circuit breaker

Replace fuse or reset circuit breaker and check amps

Broken fan belt

Replace

Defective motor or capacitor

Replace

Motor starter overloaded

Reset starter and check amps

Motor overamps

Airflow too high

Check airflow and adjust drives if needed

Static pressures are higher or lower 

than design

If higher, ductwork should be improved

If lower, fan RPMs should be lower

Blower rotation is incorrect

Check rotation and correct

Motor voltage incorrect

Check motor nameplate and supplied voltage

Motor horsepower too low

See specifications and catalog for fan curves to determine 

if horsepower is sufficient

Shorted windings in motor

Replace motor

Insufficient airflow

Mixing box damper not fully open

Adjust damper linkage or replace damper motor

System static pressure too high

Improve ductwork to eliminate losses using good duct 

practices

Blower speed too low

Check for correct drives and RPMs with catalog data

Mixing box dampers closed

Open and adjust

Dirty or clogged filters

Clean or replace

Leaks in ductwork

Repair

Elbows, or other obstructions may 

restrict fan outlet

Correct or improve ductwork

Belt slippage

Adjust belt tension

Unit running backwards

Correct as shown in System Start-Up section, Step #2, 

page 10

Excessive dirt buildup on wheels

Clean wheel

Too much airflow

Blower fan speed too high

Check for correct fan RPM

Filter(s) not in place

Install filters

Insufficient static pressure

(airflow resistance)

Induce static pressure into system ductwork

Excessive noise or 

vibration

Wheel improperly aligned and rubbing on 

housing

Center wheel

Loose wheel on shaft

Tighten wheel setscrew

Loose motor or blower sheave

Tighten sheave setscrew

Belts too loose

Adjust belt tension after 24 hours of operation

Belts too tight

Loosen to maintain 3/8 inch deflection per ft. of span 

between sheaves

Worn belt

Replace 

Motor base or blower loose

Tighten mountings bolts

Worn bearings 

Replace

Bearing and drive alignment

Realign

Motor out of balance

Replace

Unbalanced wheel caused by excessive 

dirt and grease buildup

Replace or rebalance

Sheaves eccentric or out-of-balance

Replace or rebalance

Accumulation of material on wheel

Clean wheel and housing

Foreign objects in wheel or housing

Remove objects. Check for damage or unbalance.

Troubleshooting

NOTE

Before taking any corrective action, ensure unit is incapable of operation during repairs.

Содержание MSCF-BI

Страница 1: ...ation and Maintenance Manual Please read and save these instructions Read carefully before attempting to assemble install operate or maintain the product described Protect yourself and others by obser...

Страница 2: ...are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The c...

Страница 3: ...Electric Heater 15 Maintenance Fan 16 Coil 16 Drain Pan 16 Reference Start Up Documentation 17 Maintenance Log 18 19 Warranty Backcover Unit Layout 1 Fan and Cabinet Section 2 Cooling Section Chilled...

Страница 4: ...3 0 inch 3 8 16 Spinlock Nut Two required per assembly 3 8 16 Spinlock Nut Two required per assembly HANGING ASSEMBLY BASE ASSEMBLY Mounting Instructions Greenheck s Modular Small Cabinet Fan MSCF sho...

Страница 5: ...4 Row HW Steam 15 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 20 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 25 6 75 21 18 5 6 75 6 75 21 6 75 9 5 18 5 23 38 2 5 3 5...

Страница 6: ...ertical Quantity Face Area Sloped Quantity Face Area 15 9x18 2 1 8 12x12 1 2 5 12x24 1 20 12x12 1 2 5 16x16 1 3 4 12x24 1 16x20 1 25 14x18 2 3 0 16x20 2 3 8 30 16x16 1 3 4 12x24 1 5 3 16x20 1 24x24 1...

Страница 7: ...15 50 9 38 3 188 1 375 4 0 26 0 85 8 6 62 12 75 9 38 3 188 1 375 4 0 26 0 All dimensions are in inches NOTE With airflow from left to right the fluid enters the coil from the bottom connection Inlet...

Страница 8: ...2 50 24 5 21 0 10 12 14 1 38 1 63 65 6 7 50 24 5 26 0 10 12 14 1 38 1 63 85 8 6 62 24 5 26 0 10 12 14 1 38 1 63 All dimensions are in inches Unit Size Face Area A B C L M N P 4 Row 6 Row 8 Row All Al...

Страница 9: ...should be capped off cap Unit Size Face Area A B C D E F G 4 Row 6 8 Row 4 Row 6 Row 8 Row 30 3 2 38 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 0 45 4 5 50 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 5 5...

Страница 10: ...rage and Fan RPM All access doors must be installed Measure and record the input voltage and motor amperage s To measure the fan RPM the blower door will need to be removed Minimize measurement time b...

Страница 11: ...ductwork Repair Elbows or other obstructions may restrict fan outlet Correct or improve ductwork Belt slippage Adjust belt tension Unit running backwards Correct as shown in System Start Up section S...

Страница 12: ...independently of the coils Undue stress should not be applied at the connection to coil headers 2 The condensate drain pipe should be sized adequately to ensure the condensate drains properly See Drai...

Страница 13: ...are recommended for low pressure steam On high pressure systems bucket traps are normally recommended The thermostatic traps should be used only for air venting 3 Bucket traps are recommended for use...

Страница 14: ...he requirements and practices described below are based on the National Electric Code NEC and The Space Heating Standard of the Underwriters Laboratories Inc UL Although UL requirements are uniform th...

Страница 15: ...with the thermostat set to 70 F the heater will be off with a temperature sensing above 70 F As the temperature varies the steps turn on and off to hold the setpoint discharge temperature The colder...

Страница 16: ...n air Occasionally oil and dust may accumulate on the wheel causing imbalance When this occurs the wheel and housing should be cleaned to assure smooth and safe operation Inspect fan impeller and hous...

Страница 17: ...rated enough to prevent freeze up NOTE Carefully read instructions for mixing antifreeze solution used Some products will have a higher freezing point in their natural state than when mixed with water...

Страница 18: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Страница 19: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Страница 20: ...or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo g...

Отзывы: