background image

Roof Curb Mounting

Roof curb details including duct location dimensions, 
are available on Roof Curb Assembly Instructions, Part 
Number 472119.

Rooftop units require curbs to be mounted first. The 
duct connections must be located so they will be clear 
of structural members of the building.

1.  Factory Supplied Roof Curbs: 

Roof curbs are 

Model GKD. The GKD ships in a knockdown kit 
(includes duct adapter) and requires field assembly 
(by others). Assembly instructions are included with 
the GKD curbs.

2. Install Curb: 

Locate curb over roof opening and 

fasten in place. (Refer to Recommended Roof 
Openings). Check that the diagonal dimensions 
are within ±1/8 inch of each other and adjust as 
necessary. For proper unit operation, it is important 
that the installation be level. Shim as required 
to level. 

3. Install Ductwork: 

Installation of all ducts should 

be done in accordance with SMACNA and AMCA 
guidelines. Duct adapter provided to support ducts 
prior to setting the unit. 

4. Install Insulation: 

One-inch deep insulation 

pans were provided with the curb assembly. Install 
insulation prior to setting the unit. Insulation is not 
included from the factory.

5. Set the Unit: 

Lift unit to a point directly above the 

curb and duct openings. Guide unit while lowering 
to align with duct openings. Roof curbs fit inside the 
unit base. Make sure the unit is properly seated on 
the curb and is level.

6. Fastening: 

The installer is responsible for ensuring 

that the unit fastening methods are sufficient 
to account for the weight and size of these 
additional modules.

Unit  

Size

L

W

LF

WF

Curb Weight 

(lbs.)

ERVe-20 61.103

40.353

61.007

40.161

93

ERVe-35 63.353

48.478

63.353

48.286

106

ERVe-45 67.353

55.478

67.353

55.286

120

ERVe-55 78.228

65.416

78.228

65.224

148

All dimensions are in inches.  
Weights are for 14-inch high GKD type curbs.

W

L

W

WF

LF

L

Curb Outside Dimensions and Weights

Handling

While this unit was constructed with quality and 
dependability in mind, damage still may occur during 
handling of the unit for installation. Exercise extreme 
caution to prevent any damage from occurring to the 
refrigerant system. 

The system design and installation should follow 
accepted industry practice, such as described in 
the ASHRAE Handbook. Adequate space should be 
left around the unit for piping coils and drains, filter 
replacement, and maintenance. Sufficient space should 
be provided on the side of the unit for routine service 
and component removal should that become necessary.

Lifting

  1.  Before lifting, be sure that all shipping material has 

been removed from unit.

  2.  To assist in determining rigging requirements, 

weights are shown below.

  3.  Unit must be lifted by all corner lifting points 

provided on base structure.

  4.  Rigger to use suitable mating hardware to attach to 

unit corner lifting points.

  5.  Spreader bar(s) must span the unit to prevent 

damage to the cabinet by the lift cables.

  6.  Always test-lift the unit to check for proper balance 

and rigging before hoisting to desired location.

  7.  Never lift units by weatherhoods. 

  8.  Never lift units in windy conditions.

  9.  Preparation of curb and roof openings should be 

completed prior to lifting unit to the roof.

 10.  Check to be sure that gasketing (supplied by 

others) has been applied to the curb prior to lifting 
the unit and setting on curb.

WARNING

All factory provided lifting lugs must be used when 
lifting the unit. Failure to comply with this safety 
precaution could result in property damage, serious 
injury or death.

Energy Recovery Ventilator

6

®

Содержание ERVe Series

Страница 1: ...is not exceeding the motor nameplate amps 5 Do not allow the power cable to kink or come in contact with oil grease hot surfaces or chemicals Replace cord immediately if damaged 6 Verify that the pow...

Страница 2: ...0 Routine Maintenance 21 23 Troubleshooting Economizer Alarms 24 Air ow 25 Unit 25 27 Maintenance Log Backcover Our Commitment Backcover Unit Overview Basic Unit The ERVe units are prewired such that...

Страница 3: ...ter ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for periodic...

Страница 4: ...es Door handles hinges and other protrusions are not included in the dimensions above Dimensions are rounded up to the nearest 1 inch Duct Dimensions Unit Size A B C D E F G H ERVe 20 11 8 18 0 12 2 1...

Страница 5: ...h must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A Unit Size A B Approx Weight lbs ERVe 20 22 37 950 ERVe 35 25 44 5 1270 ERVe 45...

Страница 6: ...53 48 286 106 ERVe 45 67 353 55 478 67 353 55 286 120 ERVe 55 78 228 65 416 78 228 65 224 148 All dimensions are in inches Weights are for 14 inch high GKD type curbs W L W WF LF L Curb Outside Dimens...

Страница 7: ...based on 100 effective duct length requirements as prescribed in AMCA Publication 201 Calculated values have been rounded up to nearest foot Ductwork Connections Examples of poor and good fan to duct...

Страница 8: ...le in the cabinet bottom and wire to the disconnect switch Seal penetration in cabinet bottom to prevent leakage The electric supply to the unit must meet stringent requirements for the system to oper...

Страница 9: ...carrying the supply power Make sure that eld supplied conduit does not interfere with access panel operation If wire resistance exceeds 0 75 ohms an industrial style plug in relay should be added to...

Страница 10: ...tion sensor light NC C NO NC C NO SUPPLY DIRTY FILTER SWITCH EXHAUST DIRTY FILTER SWITCH DIRTY FILTER HOT COMMON 24V SEC Dirty Filter Indicator powered by others C C C R R R G 4 Y1 6 7 12 S6 ECONOMIZE...

Страница 11: ...ptured Exhaust Only Operation This option allows for the exhaust fan to run continuously while the supply fan is off Frost Control Extremely cold outdoor air temperatures can cause moisture condensati...

Страница 12: ...eel should stop rotating the sensor will close a set of contacts in the unit control center Field wiring of a light or other alarm between terminals R and 12 in the unit control center will notify mai...

Страница 13: ...__________________________ Phone Number _______________________________ Pre Start Up Checklist check as items are completed Disconnect and lock out all power switches Remove any foreign objects that a...

Страница 14: ...s No N A Yes No OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Remote Control Panel Yes No N A Variable...

Страница 15: ...nd belts for proper alignment to avoid unnecessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in this section Fan Belt Installati...

Страница 16: ...by opening door slightly remove lters if necessary to view wheel the wheel should rotate freely at about 20 40 RPM Energy Recovery Wheel The ERVe models contain a total energy recovery wheel The whee...

Страница 17: ...ton to increase change the displayed parameter value 7 Press enter to accept the displayed value and store it in non volatile RAM 8 CHANGE STORED displays 9 Press enter to return the current menu para...

Страница 18: ...PARAMETER A1 01 CHANGE TO 2 PARAMETER d1 02 FOR NEW 40Hz SETTING PARAMETER d1 01 FOR NEW 60Hz SETTING PARAMETER d1 03 FOR NEW 30Hz SETTING PARAMETER A1 01 CHANGE TO 0 USER TO PROVIDE CONTACTS AND ISO...

Страница 19: ...multiple speed settings Open Drive runs at 60 Hz SC to S4 Drive runs at 40 Hz SC to S5 Drive runs at 30 Hz CO2 Sensor Set Point Control A carbon dioxide sensor is provided from the factory for field m...

Страница 20: ...n 0 6 C6 02 Carrier Frequency 2 D2 01 Ref Upper Limit 40 or 50 D2 02 Ref Lower Limit 5 E2 01 Motor Rated FLA Motor FLA E2 03 Motor No Load Current Must be less than FLA H1 02 Multi Function Input Term...

Страница 21: ...tors Motor maintenance is generally limited to cleaning and lubrication Cleaning should be limited to exterior surfaces only Removing dust and grease buildup on the motor housing assists proper motor...

Страница 22: ...ds upon the cleanliness of the incoming air These lters should be cleaned prior to start up Clean lters by rinsing with a mild detergent in warm water Outdoor Air Filters Access to the outdoor air lte...

Страница 23: ...sh remove any heavier accumulation A detergent water solution can also be used Avoid aggressive organic solvents such as acetone The energy recovery wheel segments can be soaked in the above solution...

Страница 24: ...denti ed and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired alarm 2 Press the enter 3...

Страница 25: ...information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SMACNA and AMCA guidelines Unit 1 Unit 2 Unit 3 Unit 4 Model Number...

Страница 26: ...lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check motor namepl...

Страница 27: ...heel motor overloads are tripping due to rubbing between wheel and air seals Recheck air seals make sure they are not too tight See Energy Recovery Wheel under Unit Start Up Section Excessive noise or...

Страница 28: ...tes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ __...

Отзывы: