background image

Dampers

Check all dampers to ensure they open and close 
properly and without binding. Backdraft dampers 
can be checked by hand to determine if blades open 
and close freely. Apply power to motorized dampers 
to ensure the actuator opens and closes the damper 
as designed.

Fan Belts

Belts must be checked on a regular basis for wear, 
tension, alignment, and dirt accumulation. Premature 
or frequent belt failures can be caused by improper 
belt tension (either too loose or too tight) or misaligned 
sheaves. Abnormally high belt tension or drive 
misalignment will cause excessive bearing loads and 
may result in failure of the fan and/or motor bearings. 
Conversely, loose belts will cause squealing on start-up, 
excessive belt flutter, slippage, and overheated sheaves. 
Both loose and tight belts can cause fan vibration.

When replacing belts on multiple groove drives, all belts 
should be changed to provide uniform drive loading. Do 
not pry belts on or off the sheave. Loosen belt tension 
until belts can be removed by simply lifting the belts off 
the sheaves. After replacing belts, ensure that slack in 
each belt is on the same side of the drive. Belt dressing 
should never be used.

Do not install new belts on worn sheaves. If the sheaves 
have grooves worn in them, they must be replaced 
before new belts are installed.

The proper belt setting is the lowest tension at which 
the belts will not slip under peak load operation. For 
initial tensioning, set the belt deflection at 1/64- inch 
for each inch of belt span (measured half-way between 
sheave centers). For example, if the belt span is 64 
inches, the belt deflection should be one inch (using 
moderate thumb 
pressure at mid-point 
of the drive). Check 
belt tension two times 
during the first 24 hours 
of operation and 
periodically thereafter.

Fan Motors

Motor maintenance is generally limited to cleaning 
and lubrication. Cleaning should be limited to exterior 
surfaces only. Removing dust and grease buildup on 
the motor housing assists proper motor cooling. Never 
wash-down motor with 
high pressure spray. 
Greasing of motors is only 
intended when fittings 
are provided. Many 
fractional motors are 
permanently lubricated 
for life and require no 
further lubrication.

Routine Maintenance

DANGER

Electric shock hazard. Can cause injury or death. 
Before attempting to perform any service or 
maintenance, turn the electrical power to unit to OFF 
at disconnect switch(es). Unit may have multiple 
power supplies.

CAUTION

Use caution when removing access panels or other 
unit components, especially while standing on a 
ladder or other potentially unsteady base. Access 
panels and unit components can be heavy and 
serious injury may occur.

Once the unit has been put into operation, a routine 
maintenance program should be set up to preserve 
reliability and performance. Items to be included in this 
program are:

Lubrication 

Apply lubrication where required

Dampers 

Check for unobstructed operation

Fan Belts 

Check for wear, tension, alignment

Motors 

Check for cleanliness

Blower Wheel & Fasteners 

Check for cleanliness 
Check all fasteners for tightness 
Check for fatigue, corrosion, wear

Bearings 

Check for cleanliness 
Check set screws for tightness 
Lubricate as required

External Filter 

Check for cleanliness - clean if required

Internal Filter 

Check for cleanliness - replace if required

Door Seal 

Check if intact and pliable

Energy Recovery Wheel 

Check for cleanliness - clean if required 
Check belt for wear 
Check pulley, bearings, and motor

Maintenance Procedures:

Lubrication

Check all moving components for proper lubrication. 
Apply lubrication where required. Any components 
showing excessive wear should be replaced to maintain 
the integrity of the unit and ensure proper operation.

Belt Span

Deflection = 

Belt Span

64

Energy Recovery Ventilator

21

®

Содержание ERVe Series

Страница 1: ...is not exceeding the motor nameplate amps 5 Do not allow the power cable to kink or come in contact with oil grease hot surfaces or chemicals Replace cord immediately if damaged 6 Verify that the pow...

Страница 2: ...0 Routine Maintenance 21 23 Troubleshooting Economizer Alarms 24 Air ow 25 Unit 25 27 Maintenance Log Backcover Our Commitment Backcover Unit Overview Basic Unit The ERVe units are prewired such that...

Страница 3: ...ter ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for periodic...

Страница 4: ...es Door handles hinges and other protrusions are not included in the dimensions above Dimensions are rounded up to the nearest 1 inch Duct Dimensions Unit Size A B C D E F G H ERVe 20 11 8 18 0 12 2 1...

Страница 5: ...h must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A Unit Size A B Approx Weight lbs ERVe 20 22 37 950 ERVe 35 25 44 5 1270 ERVe 45...

Страница 6: ...53 48 286 106 ERVe 45 67 353 55 478 67 353 55 286 120 ERVe 55 78 228 65 416 78 228 65 224 148 All dimensions are in inches Weights are for 14 inch high GKD type curbs W L W WF LF L Curb Outside Dimens...

Страница 7: ...based on 100 effective duct length requirements as prescribed in AMCA Publication 201 Calculated values have been rounded up to nearest foot Ductwork Connections Examples of poor and good fan to duct...

Страница 8: ...le in the cabinet bottom and wire to the disconnect switch Seal penetration in cabinet bottom to prevent leakage The electric supply to the unit must meet stringent requirements for the system to oper...

Страница 9: ...carrying the supply power Make sure that eld supplied conduit does not interfere with access panel operation If wire resistance exceeds 0 75 ohms an industrial style plug in relay should be added to...

Страница 10: ...tion sensor light NC C NO NC C NO SUPPLY DIRTY FILTER SWITCH EXHAUST DIRTY FILTER SWITCH DIRTY FILTER HOT COMMON 24V SEC Dirty Filter Indicator powered by others C C C R R R G 4 Y1 6 7 12 S6 ECONOMIZE...

Страница 11: ...ptured Exhaust Only Operation This option allows for the exhaust fan to run continuously while the supply fan is off Frost Control Extremely cold outdoor air temperatures can cause moisture condensati...

Страница 12: ...eel should stop rotating the sensor will close a set of contacts in the unit control center Field wiring of a light or other alarm between terminals R and 12 in the unit control center will notify mai...

Страница 13: ...__________________________ Phone Number _______________________________ Pre Start Up Checklist check as items are completed Disconnect and lock out all power switches Remove any foreign objects that a...

Страница 14: ...s No N A Yes No OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Remote Control Panel Yes No N A Variable...

Страница 15: ...nd belts for proper alignment to avoid unnecessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in this section Fan Belt Installati...

Страница 16: ...by opening door slightly remove lters if necessary to view wheel the wheel should rotate freely at about 20 40 RPM Energy Recovery Wheel The ERVe models contain a total energy recovery wheel The whee...

Страница 17: ...ton to increase change the displayed parameter value 7 Press enter to accept the displayed value and store it in non volatile RAM 8 CHANGE STORED displays 9 Press enter to return the current menu para...

Страница 18: ...PARAMETER A1 01 CHANGE TO 2 PARAMETER d1 02 FOR NEW 40Hz SETTING PARAMETER d1 01 FOR NEW 60Hz SETTING PARAMETER d1 03 FOR NEW 30Hz SETTING PARAMETER A1 01 CHANGE TO 0 USER TO PROVIDE CONTACTS AND ISO...

Страница 19: ...multiple speed settings Open Drive runs at 60 Hz SC to S4 Drive runs at 40 Hz SC to S5 Drive runs at 30 Hz CO2 Sensor Set Point Control A carbon dioxide sensor is provided from the factory for field m...

Страница 20: ...n 0 6 C6 02 Carrier Frequency 2 D2 01 Ref Upper Limit 40 or 50 D2 02 Ref Lower Limit 5 E2 01 Motor Rated FLA Motor FLA E2 03 Motor No Load Current Must be less than FLA H1 02 Multi Function Input Term...

Страница 21: ...tors Motor maintenance is generally limited to cleaning and lubrication Cleaning should be limited to exterior surfaces only Removing dust and grease buildup on the motor housing assists proper motor...

Страница 22: ...ds upon the cleanliness of the incoming air These lters should be cleaned prior to start up Clean lters by rinsing with a mild detergent in warm water Outdoor Air Filters Access to the outdoor air lte...

Страница 23: ...sh remove any heavier accumulation A detergent water solution can also be used Avoid aggressive organic solvents such as acetone The energy recovery wheel segments can be soaked in the above solution...

Страница 24: ...denti ed and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired alarm 2 Press the enter 3...

Страница 25: ...information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SMACNA and AMCA guidelines Unit 1 Unit 2 Unit 3 Unit 4 Model Number...

Страница 26: ...lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check motor namepl...

Страница 27: ...heel motor overloads are tripping due to rubbing between wheel and air seals Recheck air seals make sure they are not too tight See Energy Recovery Wheel under Unit Start Up Section Excessive noise or...

Страница 28: ...tes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ __...

Отзывы: