Receiving

This product may have been subject to road salt 
during transit. If so, immediately wash off all visible 
white reside from all exterior surfaces. Upon receiving 
the product, check to ensure all items are accounted 
for by referencing the delivery receipt or packing list. 
Inspect each crate or carton for shipping damage before 
accepting delivery. Alert the carrier if any damage is 
detected, 

do not refuse shipment

. The customer shall 

make notation of damage (or shortage of items) on the 
delivery receipt and all copies of the bill of lading which 
should be countersigned by the delivering carrier. If 
damaged, immediately contact your manufacturer’s 
representative. Any physical damage to the unit after 
acceptance is not the responsibility of the manufacturer.

Handling

Units are to be rigged and moved by the lifting brackets 
provided or by the skid when a forklift is used. Location 
of brackets varies by model and size. Handle in such 
a manner as to keep from scratching or chipping the 
coating. Damaged finish may reduce ability of unit to 
resist corrosion.

Unpacking

Verify that all required parts and the correct quantity 
of each item have been received. If any items are 
missing, report shortages to your local representative to 
arrange for obtaining missing parts. Sometimes it is not 
possible that all items for the unit be shipped together 
due to availability of transportation and truck space. 
Confirmation of shipment(s) must be limited to only 
items on the bill of lading.

Storage

Units are protected against damage during shipment. If 
the unit cannot be installed and operated immediately, 
precautions need to be taken to prevent deterioration of 
the unit during storage. The user assumes responsibility 
of the unit and accessories while in storage. The 
manufacturer will not be responsible for damage during 
storage. These suggestions are provided solely as a 
convenience to the user.

The ideal environment for the storage of units and 
accessories is indoors, above grade, in a low humidity 
atmosphere which is sealed to prevent the entry of 
blowing dust, rain, or snow. Units designed for outdoor 
applications may be stored outdoors. All accessories 
must be stored indoors in a clean, dry atmosphere. 

Indoor

Maintain temperatures evenly to prevent condensation. 
Remove any accumulations of dirt, water, ice, or snow 
and wipe dry before moving to indoor storage. To 
avoid condensation, allow cold parts to reach room 
temperature. Leave coverings loose to permit air 
circulation and to allow for periodic inspection.

The unit should be stored at least 3½ in. (89 mm) off 
the floor. Clearance should be provided to permit air 
circulation and space for inspection.

Outdoor

The unit should be placed on a level surface to prevent 
water from leaking into the unit. The unit should be 
elevated so that it is above water and snow levels. 
Ensure sufficient support to prevent unit from settling 
into soft ground. Locate parts far enough apart to 
permit air circulation, sunlight, and space for periodic 
inspection. To minimize water accumulation, place all 
unit parts on blocking supports so that rain water will 
run off.

Do not cover parts with plastic film or tarps as these 
cause condensation of moisture from the air passing 
through heating and cooling cycles.

Inspection and Maintenance

While in storage, inspect units once per month. Keep a 
record of inspection and maintenance performed.

If moisture or dirt accumulations are found on parts, 
the source should be located and eliminated. At each 
inspection, rotate the fan wheel by hand ten to fifteen 
revolutions to distribute lubricant on motor. If paint 
deterioration begins, consideration should be given to 
touch-up or repainting. Units with special coatings may 
require special techniques for touch-up or repair.

Machined parts coated with rust preventive should be 
restored to good condition promptly if signs of rust 
occur. Immediately remove the original rust preventive 
coating with petroleum solvent and clean with lint-free 
cloths. Polish any remaining rust from surface with 
crocus cloth or fine emery paper and oil. Do not destroy 
the continuity of the surfaces. Wipe thoroughly clean 
with Tectyl

®

 506 (Ashland Inc.) or the equivalent. For 

hard to reach internal surfaces or for occasional use, 
consider using Tectyl

®

 511M Rust Preventive, WD-40

® 

or the equivalent.

Removing from Storage

As units are removed from storage to be installed 
in their final location, they should be protected and 
maintained in a similar fashion until the equipment goes 
into operation.

Prior to installing the unit and system components, 
inspect the unit assembly to make sure it is in working 
order.

1.  Check all fasteners, set screws on the fan, wheel, 

bearings, drive, motor base, and accessories for 
tightness.

2.  Rotate the fan wheel(s) by hand and assure no parts 

are rubbing.

Energy Recovery Ventilator

3

®

Содержание ERVe Series

Страница 1: ...is not exceeding the motor nameplate amps 5 Do not allow the power cable to kink or come in contact with oil grease hot surfaces or chemicals Replace cord immediately if damaged 6 Verify that the pow...

Страница 2: ...0 Routine Maintenance 21 23 Troubleshooting Economizer Alarms 24 Air ow 25 Unit 25 27 Maintenance Log Backcover Our Commitment Backcover Unit Overview Basic Unit The ERVe units are prewired such that...

Страница 3: ...ter ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for periodic...

Страница 4: ...es Door handles hinges and other protrusions are not included in the dimensions above Dimensions are rounded up to the nearest 1 inch Duct Dimensions Unit Size A B C D E F G H ERVe 20 11 8 18 0 12 2 1...

Страница 5: ...h must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A Unit Size A B Approx Weight lbs ERVe 20 22 37 950 ERVe 35 25 44 5 1270 ERVe 45...

Страница 6: ...53 48 286 106 ERVe 45 67 353 55 478 67 353 55 286 120 ERVe 55 78 228 65 416 78 228 65 224 148 All dimensions are in inches Weights are for 14 inch high GKD type curbs W L W WF LF L Curb Outside Dimens...

Страница 7: ...based on 100 effective duct length requirements as prescribed in AMCA Publication 201 Calculated values have been rounded up to nearest foot Ductwork Connections Examples of poor and good fan to duct...

Страница 8: ...le in the cabinet bottom and wire to the disconnect switch Seal penetration in cabinet bottom to prevent leakage The electric supply to the unit must meet stringent requirements for the system to oper...

Страница 9: ...carrying the supply power Make sure that eld supplied conduit does not interfere with access panel operation If wire resistance exceeds 0 75 ohms an industrial style plug in relay should be added to...

Страница 10: ...tion sensor light NC C NO NC C NO SUPPLY DIRTY FILTER SWITCH EXHAUST DIRTY FILTER SWITCH DIRTY FILTER HOT COMMON 24V SEC Dirty Filter Indicator powered by others C C C R R R G 4 Y1 6 7 12 S6 ECONOMIZE...

Страница 11: ...ptured Exhaust Only Operation This option allows for the exhaust fan to run continuously while the supply fan is off Frost Control Extremely cold outdoor air temperatures can cause moisture condensati...

Страница 12: ...eel should stop rotating the sensor will close a set of contacts in the unit control center Field wiring of a light or other alarm between terminals R and 12 in the unit control center will notify mai...

Страница 13: ...__________________________ Phone Number _______________________________ Pre Start Up Checklist check as items are completed Disconnect and lock out all power switches Remove any foreign objects that a...

Страница 14: ...s No N A Yes No OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Remote Control Panel Yes No N A Variable...

Страница 15: ...nd belts for proper alignment to avoid unnecessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in this section Fan Belt Installati...

Страница 16: ...by opening door slightly remove lters if necessary to view wheel the wheel should rotate freely at about 20 40 RPM Energy Recovery Wheel The ERVe models contain a total energy recovery wheel The whee...

Страница 17: ...ton to increase change the displayed parameter value 7 Press enter to accept the displayed value and store it in non volatile RAM 8 CHANGE STORED displays 9 Press enter to return the current menu para...

Страница 18: ...PARAMETER A1 01 CHANGE TO 2 PARAMETER d1 02 FOR NEW 40Hz SETTING PARAMETER d1 01 FOR NEW 60Hz SETTING PARAMETER d1 03 FOR NEW 30Hz SETTING PARAMETER A1 01 CHANGE TO 0 USER TO PROVIDE CONTACTS AND ISO...

Страница 19: ...multiple speed settings Open Drive runs at 60 Hz SC to S4 Drive runs at 40 Hz SC to S5 Drive runs at 30 Hz CO2 Sensor Set Point Control A carbon dioxide sensor is provided from the factory for field m...

Страница 20: ...n 0 6 C6 02 Carrier Frequency 2 D2 01 Ref Upper Limit 40 or 50 D2 02 Ref Lower Limit 5 E2 01 Motor Rated FLA Motor FLA E2 03 Motor No Load Current Must be less than FLA H1 02 Multi Function Input Term...

Страница 21: ...tors Motor maintenance is generally limited to cleaning and lubrication Cleaning should be limited to exterior surfaces only Removing dust and grease buildup on the motor housing assists proper motor...

Страница 22: ...ds upon the cleanliness of the incoming air These lters should be cleaned prior to start up Clean lters by rinsing with a mild detergent in warm water Outdoor Air Filters Access to the outdoor air lte...

Страница 23: ...sh remove any heavier accumulation A detergent water solution can also be used Avoid aggressive organic solvents such as acetone The energy recovery wheel segments can be soaked in the above solution...

Страница 24: ...denti ed and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired alarm 2 Press the enter 3...

Страница 25: ...information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SMACNA and AMCA guidelines Unit 1 Unit 2 Unit 3 Unit 4 Model Number...

Страница 26: ...lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check motor namepl...

Страница 27: ...heel motor overloads are tripping due to rubbing between wheel and air seals Recheck air seals make sure they are not too tight See Energy Recovery Wheel under Unit Start Up Section Excessive noise or...

Страница 28: ...tes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ __...

Отзывы: