background image

Economizer

Relevant Set Points

  1.  MAT SET   The mixed air temperature set point 

after the energy wheel. The control will modulate 
the energy wheel to maintain temperature as best 
as it can. (Set point menu, default 53°F )

  2.  LOW T LOCK   The set point for the low 

temperature mechanical cooling lockout. (Set point 
menu, default 32°F) 

  3.  DRYBLB SET   The outdoor air set point to call for 

economizer. (Set point menu, default 63°F)

  4.  MIN POS   The minimum signal voltage sent to the 

energy wheel. This must be set to 2 VDC. (Set point 
menu, default 2.8 VDC)

  5.  AUX1 O   The controllers operating sequence 

structure. (Set point menu, default ‘None’)

  6.  ERV OAT SP   The set point for low temperature 

economizer lockout. This is the low temperature set 
point when AUX1 O is set to ERV. (Set point menu, 
default 32°F)

  7.  STG3 DLY   Time delay after second cooling stage 

is enabled (Advanced setup menu, default 2 hrs.)

Using the Keypad with Settings and 
Parameters

To use the keypad when working with Set points, 
System and Advanced Settings, Checkout tests, and 
Alarms: 

  1.  Navigate to the desired menu.

 2.  Press   (enter) to display the first item in the 

currently displayed menu.

 3.  Use the   and   buttons to scroll to the desired 

parameter.

 4.  Press   (enter) to display the value of the currently 

displayed item.

 5.  Press the   button to increase (change) the 

displayed parameter value.*

 6.  Press the   button to increase (change) the 

displayed parameter value.*

 7.  Press   (enter) to accept the displayed value and 

store it in non-volatile RAM.

  8.  CHANGE STORED displays.

 9.  Press   (enter) to return the current menu 

parameter. 

 10. Press   (escape) to return to the current menu 

parameter.

 

  * When values are displayed, pressing and holding 

the   or   button causes the display to 
automatically increment. 

MODULATE WHEEL

STOP WHEEL

OA  

Temp

OA  

Enthalpy

OA/RA  

Temp  

Differential

OA  

Temp

OA  

Enthalpy

OA/RA  

Temp  

Differential

DRYBLB SET

X

X

MAT SET

X

X

X

X

X

X

LOW T LOCK

X

X

X

X

X

X

ERV OAT SP

X

X

X

MIN POS

X

X

X

AUX1 OUT

ERV

ERV

ERV

STG3 DLY

X

X

X

X

X

X

Stop Wheel 

  1.  Navigate to the Checkout menu and press 

  enter).

  2.  The energy wheel and cooling should stop.

  3.  Navigate to Connect ERV and press   (enter) twice 

to run the test.

  4.  Voltage between AUX1-O and C should be 24 VAC. 

The energy wheel should activate.

Modulate Wheel

  1.  Navigate to the Checkout menu and press 

  Enter).

  2.  The cooling should turn off and the wheel should 

be rotating at full speed.

  3.  Navigate to Damper Open and press   (enter) twice 

to run the test.

  4.  Voltage between terminals ACT 2-10 and ACT 

COM should be 10 VDC. This will slow the wheel 
down to minimum speed.

 5.  Press   (escape), navigate to Damper Close and 

press   (enter) twice to run the test.

  6.  Voltage between terminal ACT 2-10 and ACT COM 

should be 2 VDC. This will speed the wheel up to 
maximum speed.

The table shows which set points are relevant to the 
given sequences. Refer to the wiring diagram for the 
units’s sequence.

Energy Recovery Ventilator

17

®

Содержание ERVe Series

Страница 1: ...is not exceeding the motor nameplate amps 5 Do not allow the power cable to kink or come in contact with oil grease hot surfaces or chemicals Replace cord immediately if damaged 6 Verify that the pow...

Страница 2: ...0 Routine Maintenance 21 23 Troubleshooting Economizer Alarms 24 Air ow 25 Unit 25 27 Maintenance Log Backcover Our Commitment Backcover Unit Overview Basic Unit The ERVe units are prewired such that...

Страница 3: ...ter ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for periodic...

Страница 4: ...es Door handles hinges and other protrusions are not included in the dimensions above Dimensions are rounded up to the nearest 1 inch Duct Dimensions Unit Size A B C D E F G H ERVe 20 11 8 18 0 12 2 1...

Страница 5: ...h must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A Unit Size A B Approx Weight lbs ERVe 20 22 37 950 ERVe 35 25 44 5 1270 ERVe 45...

Страница 6: ...53 48 286 106 ERVe 45 67 353 55 478 67 353 55 286 120 ERVe 55 78 228 65 416 78 228 65 224 148 All dimensions are in inches Weights are for 14 inch high GKD type curbs W L W WF LF L Curb Outside Dimens...

Страница 7: ...based on 100 effective duct length requirements as prescribed in AMCA Publication 201 Calculated values have been rounded up to nearest foot Ductwork Connections Examples of poor and good fan to duct...

Страница 8: ...le in the cabinet bottom and wire to the disconnect switch Seal penetration in cabinet bottom to prevent leakage The electric supply to the unit must meet stringent requirements for the system to oper...

Страница 9: ...carrying the supply power Make sure that eld supplied conduit does not interfere with access panel operation If wire resistance exceeds 0 75 ohms an industrial style plug in relay should be added to...

Страница 10: ...tion sensor light NC C NO NC C NO SUPPLY DIRTY FILTER SWITCH EXHAUST DIRTY FILTER SWITCH DIRTY FILTER HOT COMMON 24V SEC Dirty Filter Indicator powered by others C C C R R R G 4 Y1 6 7 12 S6 ECONOMIZE...

Страница 11: ...ptured Exhaust Only Operation This option allows for the exhaust fan to run continuously while the supply fan is off Frost Control Extremely cold outdoor air temperatures can cause moisture condensati...

Страница 12: ...eel should stop rotating the sensor will close a set of contacts in the unit control center Field wiring of a light or other alarm between terminals R and 12 in the unit control center will notify mai...

Страница 13: ...__________________________ Phone Number _______________________________ Pre Start Up Checklist check as items are completed Disconnect and lock out all power switches Remove any foreign objects that a...

Страница 14: ...s No N A Yes No OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Remote Control Panel Yes No N A Variable...

Страница 15: ...nd belts for proper alignment to avoid unnecessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in this section Fan Belt Installati...

Страница 16: ...by opening door slightly remove lters if necessary to view wheel the wheel should rotate freely at about 20 40 RPM Energy Recovery Wheel The ERVe models contain a total energy recovery wheel The whee...

Страница 17: ...ton to increase change the displayed parameter value 7 Press enter to accept the displayed value and store it in non volatile RAM 8 CHANGE STORED displays 9 Press enter to return the current menu para...

Страница 18: ...PARAMETER A1 01 CHANGE TO 2 PARAMETER d1 02 FOR NEW 40Hz SETTING PARAMETER d1 01 FOR NEW 60Hz SETTING PARAMETER d1 03 FOR NEW 30Hz SETTING PARAMETER A1 01 CHANGE TO 0 USER TO PROVIDE CONTACTS AND ISO...

Страница 19: ...multiple speed settings Open Drive runs at 60 Hz SC to S4 Drive runs at 40 Hz SC to S5 Drive runs at 30 Hz CO2 Sensor Set Point Control A carbon dioxide sensor is provided from the factory for field m...

Страница 20: ...n 0 6 C6 02 Carrier Frequency 2 D2 01 Ref Upper Limit 40 or 50 D2 02 Ref Lower Limit 5 E2 01 Motor Rated FLA Motor FLA E2 03 Motor No Load Current Must be less than FLA H1 02 Multi Function Input Term...

Страница 21: ...tors Motor maintenance is generally limited to cleaning and lubrication Cleaning should be limited to exterior surfaces only Removing dust and grease buildup on the motor housing assists proper motor...

Страница 22: ...ds upon the cleanliness of the incoming air These lters should be cleaned prior to start up Clean lters by rinsing with a mild detergent in warm water Outdoor Air Filters Access to the outdoor air lte...

Страница 23: ...sh remove any heavier accumulation A detergent water solution can also be used Avoid aggressive organic solvents such as acetone The energy recovery wheel segments can be soaked in the above solution...

Страница 24: ...denti ed and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired alarm 2 Press the enter 3...

Страница 25: ...information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SMACNA and AMCA guidelines Unit 1 Unit 2 Unit 3 Unit 4 Model Number...

Страница 26: ...lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check motor namepl...

Страница 27: ...heel motor overloads are tripping due to rubbing between wheel and air seals Recheck air seals make sure they are not too tight See Energy Recovery Wheel under Unit Start Up Section Excessive noise or...

Страница 28: ...tes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ __...

Отзывы: