PREVENTATIVE MAINTENANCE:
I. Humidifier Control Panel:
A) Every 2 – 3 years:
1. at the end or beginning of the season
the inside of the tank with a clean and non
down each of the discs as well. To take the tank l
pipe coupling (and inlet supply if the unit is a supply side unit) then loosen
all the wing nuts and disconnect the fan wires at either the terminal or at the
fan.
Total time estimated:
B) Every 5 years:
1. verify the output is adequate by observing the unit under operation and
making sure all the UPC discs that should be running are indeed doing so.
You may do this by observing the operation with a flash light and peering
through the plastic lid or takin
the unit on briefly (for 3
NOT EVER JUMP OUT THE LOW WATER FLOAT SWITCHES.
2. remember that the 1000 series
To determine whether how many are on line for your particular unit
how many pairs of #6 and #7 wires are attached to the terminal switch. You
may have one or two spare banks (each bank has a capacity of
approximately 3 lbs/hr of gross fog productio
load for your unit. If you observe any non
add one of the spare banks by attaching their #6 & #7 lines to the terminals.
3. replace the float switch tank. Call the Factory for a replacement.
II. RO System:
A) Annually:
1. Replace the filters and the membrane on the RO Plant.
Total time estimated:
PREVENTATIVE MAINTENANCE:
at the end or beginning of the season take the tank lid off and wipe down
the inside of the tank with a clean and non-abrasive rag. Make sure to wipe
down each of the discs as well. To take the tank lid off disconnect the supply
pipe coupling (and inlet supply if the unit is a supply side unit) then loosen
all the wing nuts and disconnect the fan wires at either the terminal or at the
Total time estimated:
30 Minutes
1. verify the output is adequate by observing the unit under operation and
making sure all the UPC discs that should be running are indeed doing so.
You may do this by observing the operation with a flash light and peering
through the plastic lid or taking the lid off (see above instructions) and turning
the unit on briefly (for 3 – 5 seconds) WATER MUST BE IN THE TANK
NOT EVER JUMP OUT THE LOW WATER FLOAT SWITCHES.
2. remember that the 1000 series can have multiple output levels possible.
etermine whether how many are on line for your particular unit
how many pairs of #6 and #7 wires are attached to the terminal switch. You
may have one or two spare banks (each bank has a capacity of
approximately 3 lbs/hr of gross fog production) depending on the required
load for your unit. If you observe any non-performing UPCs then you may
add one of the spare banks by attaching their #6 & #7 lines to the terminals.
3. replace the float switch tank. Call the Factory for a replacement.
1. Replace the filters and the membrane on the RO Plant.
Total time estimated:
15 minutes
11
take the tank lid off and wipe down
abrasive rag. Make sure to wipe
id off disconnect the supply
pipe coupling (and inlet supply if the unit is a supply side unit) then loosen
all the wing nuts and disconnect the fan wires at either the terminal or at the
1. verify the output is adequate by observing the unit under operation and
making sure all the UPC discs that should be running are indeed doing so.
You may do this by observing the operation with a flash light and peering
g the lid off (see above instructions) and turning
5 seconds) WATER MUST BE IN THE TANK – DO
NOT EVER JUMP OUT THE LOW WATER FLOAT SWITCHES.
output levels possible.
etermine whether how many are on line for your particular unit simply see
how many pairs of #6 and #7 wires are attached to the terminal switch. You
may have one or two spare banks (each bank has a capacity of
n) depending on the required
performing UPCs then you may
add one of the spare banks by attaching their #6 & #7 lines to the terminals.
3. replace the float switch tank. Call the Factory for a replacement.