GREE Air-ccoled Closed Control Unit Service Manual
54
/Y%, if the corrected value of temperature probe is set to be x
℃
, the temperature tested by the
unit is X+x
℃
; if the corrected value of humidity probe is set to be y%, the humidity tested by the
unit is Y+y%. For example, if the ambient temperature and humidity is 23
℃
/55%, and the
temperature and humidity tested by the unit is 23.2
℃
/52%, the corrected value of temperature
probe shall be -0.2
℃
and the corrected value of humidity probe shall be 3%
Slightly press the button “Default Restore” and a window will pop up. Press “Enter” to
restore ex-factory setting or press “ESC” to cancel the request.
Slightly press the button “Function Shield” to activate shield function against heating,
energy saving, humidifying or antistatic. Once the setting is changed, it is enabled. On the
pop-up page, slightly press the character “Shield”of “Function Shield” on the top left corner, then
the capacity switch code value of each module will be displayed.
(
3
)
Module Service Time
Slightly press the button “Run Time” to view the accumulated service time of each module and
its subsidiary parts. Slightly touch the button “Reset” to clear the service time of the
corresponding module or its parts. Note: Clearing the accumated service time will affect
module’s operation!
(
4
)
Manual Debugging
Содержание JKFD15CR/Na-M
Страница 4: ...GREE Air ccoled Closed Control Unit Service Manual 1 Product Indoor Unit Outdoor Unit...
Страница 63: ...GREE Air ccoled Closed Control Unit Service Manual 60...
Страница 97: ...GREE Air ccoled Closed Control Unit Service Manual 94 2 2 Low Pressure Protection of Compressor...
Страница 101: ...GREE Air ccoled Closed Control Unit Service Manual 98 2 8 Low Air Pressure Malfunction of Indoor Fan...
Страница 102: ...GREE Air ccoled Closed Control Unit Service Manual 99 2 9 Alarm for Blocking Filter...
Страница 115: ...GREE Air ccoled Closed Control Unit Service Manual 112 4 2 8 Outdoor Unit JKFD13 NaA M O JKFD19 NaA M O...