GREE Air-ccoled Closed Control Unit Service Manual
103
4. Power Distribution of the Unit
4.1 Power Distribution Diagram
4.1.1 Phase Reversal Protector
(
1
)
Protection conditions: Input terminal of power supply for the protector is phase
reversal;
(
2
)
Result of activation: The complete unit is de-energized and can’t be turned on;
(
3
)
Treatment: Adjust wire sequence of power patch board. Check if the voltage of
three-phase power is normal.
4.1.2 Thermal Overload Relay:
(
1
)
Protection conditions: Current of motor is huge and currents of three phases are not in
balance. There is phase loss.
(
2
)
Result of activation: Overload protection of motor will be shown on wired controller;
(
3
)
Treatment: Check if winding of three phases of compressor is normal. If it's normal,
turn on the unit again and check if the working current of motor is normal.
4.1.3 Thermostat:
(
1
)
Protection conditions:Temperature of controlled parts reaches the set value;
(
2
)
Result of activation: Contact of thermostat is on or off;
Содержание JKFD15CR/Na-M
Страница 4: ...GREE Air ccoled Closed Control Unit Service Manual 1 Product Indoor Unit Outdoor Unit...
Страница 63: ...GREE Air ccoled Closed Control Unit Service Manual 60...
Страница 97: ...GREE Air ccoled Closed Control Unit Service Manual 94 2 2 Low Pressure Protection of Compressor...
Страница 101: ...GREE Air ccoled Closed Control Unit Service Manual 98 2 8 Low Air Pressure Malfunction of Indoor Fan...
Страница 102: ...GREE Air ccoled Closed Control Unit Service Manual 99 2 9 Alarm for Blocking Filter...
Страница 115: ...GREE Air ccoled Closed Control Unit Service Manual 112 4 2 8 Outdoor Unit JKFD13 NaA M O JKFD19 NaA M O...