GREE Air-ccoled Closed Control Unit Service Manual
104
(
3
)
Treatment: During normal operation, when the temperature of a controlled part
reaches the preset value, the temp sensor whose activation temperature
is fixed or adjustable will cut on or off the circuit. It can be automatically or
manually reset.
4.1.4 Overcureent Protector of Compressor:
(
1
)
Protection conditions: Current of motor is huge and currents of three phases are not in
balance. There is phase loss.
(
2
)
Result of activation: Overload protection of motor will be shown on wired controller;
(
3
)
Treatment:
:
Check if winding of three phases of compressor is normal. If it is, turn on
the unit again and check if the working current of compressor and system
pressure are normal.
4.1.5 Fusible Cutout:
(
1
)
Protection conditions: Temperature of controlled parts reaches the set value;
(
2
)
Result of activation:
:
Contact of fusible cutout is on or off;
(
3
)
Treatment:
:
During normal operation, when the temperature of a controlled part
reaches the preset value, the temp sensor whose activation temperature
is fixed or adjustable will cut on or off the circuit. It can be automatically or
manually reset.
4.1.6 AC contactor:
(
1
)
activation conditions: Coil of AC contactor is energized;
(
2
)
Result of activation: Main contact closes and load is started up.
Содержание JKFD15CR/Na-M
Страница 4: ...GREE Air ccoled Closed Control Unit Service Manual 1 Product Indoor Unit Outdoor Unit...
Страница 63: ...GREE Air ccoled Closed Control Unit Service Manual 60...
Страница 97: ...GREE Air ccoled Closed Control Unit Service Manual 94 2 2 Low Pressure Protection of Compressor...
Страница 101: ...GREE Air ccoled Closed Control Unit Service Manual 98 2 8 Low Air Pressure Malfunction of Indoor Fan...
Страница 102: ...GREE Air ccoled Closed Control Unit Service Manual 99 2 9 Alarm for Blocking Filter...
Страница 115: ...GREE Air ccoled Closed Control Unit Service Manual 112 4 2 8 Outdoor Unit JKFD13 NaA M O JKFD19 NaA M O...