GREE Air-ccoled Closed Control Unit Service Manual
82
Control the main parameter of unit (main module) and equipment (submodule) through this
interface.
Touch screen”: once select “shield” and send command, the touch screen of main module
could be shielded and “touch screen shielded” will be displayed on homepage of touch screen,
then the parameter could not be set through touch screen. Select “not to shield screen” and
send command to delete the shielding of screen.
“Clear malfunction”: when unrecoverable malfunction occurs, the malfunction could be
cleared and the unit could be reset by sending this command.
When there’s no equipment (submodule) in network view, the related setting button will be
ashing.
When select “disconnect” for communication status, related status button like ON/OFF
setting will be ashing. After the command is sent, the parameter of equipment (submodule) will
still exist in “network view” but not in “equipment parameter view”.
4.5.2 Timer control
Click Main Menu->Control-> Control in fixed time
(
or use context menu in network view
),
following dialog box will be popped up.
Содержание JKFD15CR/Na-M
Страница 4: ...GREE Air ccoled Closed Control Unit Service Manual 1 Product Indoor Unit Outdoor Unit...
Страница 63: ...GREE Air ccoled Closed Control Unit Service Manual 60...
Страница 97: ...GREE Air ccoled Closed Control Unit Service Manual 94 2 2 Low Pressure Protection of Compressor...
Страница 101: ...GREE Air ccoled Closed Control Unit Service Manual 98 2 8 Low Air Pressure Malfunction of Indoor Fan...
Страница 102: ...GREE Air ccoled Closed Control Unit Service Manual 99 2 9 Alarm for Blocking Filter...
Страница 115: ...GREE Air ccoled Closed Control Unit Service Manual 112 4 2 8 Outdoor Unit JKFD13 NaA M O JKFD19 NaA M O...