(1) Since air conditioner is type I appliance, please do conduct reliable earth treatment.
The yellow-green wire inside unit is earth wire, which can not be used for other
purpose and further not be cut off. Don’t fix it with tapping screw to avoid electric
shock.
(
2
)
Earthing resistance should match requirements of National Standard GB17790 which
is published by China government.
(3) Users’ power must offer reliable earth terminal. Please don’t connect earth wire to
following places:
①
Water pipe;
②
Gas pipe;
③
Blowing pipe;
④
Other places that professional personnel consider unreliable.
7.2 Matching Form of Power Cord and Air Switch
Model Power
Supply
Air Switch
Capacity
(
A
)
Minimum Sectional
Area
(
mm
2
)
Earthed
Cable
Power
Cord
JKFD5XXX(I)
220V
~
50Hz
63 10
10
JKFD5P/Na-E(O)
220V
~
50Hz
6 1.5
1.5
JKFD7XXX(I)
380V 3N
~
50Hz
32 4
4
JKFD7P/Na-E(O)
220V
~
50Hz
6 1.5
1.5
JKFD15XXX(I)
380V 3N
~
50Hz
40 6
6
JKFD15P/Na-M(O)
380V 3N
~
50Hz
16 1.5
1.5
JKFD20XXX(I)
380V 3N
~
50Hz
40 6
6
JKFD20P/Na-M(O)
380V 3N
~
50Hz
16 1.5
1.5
JKFD25XXX(I)
380V 3N
~
50Hz
63 16
16
JKFD13//NaA-M (O)
220V
~
50Hz
- 1.5
1.5
JKFD40XXX(I)
380V 3N
~
50Hz
100 25
25
JKFD19//NaA-M (O)
220V
~
50Hz
- 1.5
1.5
Note:
①
Specifications of circuit breaker and power cord from the above form were taken
according to the unit’s biggest current;
②
Specifications of cable from the above form were taken under the condition where
multi-core cables, whose service ambient temperature is 30 and tolerant temperature is
℃
Содержание JKFD15CR/Na-M
Страница 4: ...GREE Air ccoled Closed Control Unit Service Manual 1 Product Indoor Unit Outdoor Unit...
Страница 63: ...GREE Air ccoled Closed Control Unit Service Manual 60...
Страница 97: ...GREE Air ccoled Closed Control Unit Service Manual 94 2 2 Low Pressure Protection of Compressor...
Страница 101: ...GREE Air ccoled Closed Control Unit Service Manual 98 2 8 Low Air Pressure Malfunction of Indoor Fan...
Страница 102: ...GREE Air ccoled Closed Control Unit Service Manual 99 2 9 Alarm for Blocking Filter...
Страница 115: ...GREE Air ccoled Closed Control Unit Service Manual 112 4 2 8 Outdoor Unit JKFD13 NaA M O JKFD19 NaA M O...