81
Performance Parameters of the Unit
Remarks:
1. All the data of the cooling/heating capacity and the noise are measured before the unit is shipped out from
manufacturer.
2. All the parameters in the tables below are measured under the rated work condition. Such parameters in the
specifications are subject to change so the data on the nameplate shall govern.
●
Performance Parameters of the Outdoor Unit
Basic Model
GMV-Pdhm224W/Na-M GMV-Pdhm280W/Na-M GMV-Pdhm335W/Na-M
Power Supply
3phase,380
~
415V,50HZ,4wires system
kW
22.4
28.0
33.5
Cooling
Btu/h
76,428.8 95,536.0 114,302.0
kW
25.0 31.5 37.5
Capacity
Heating
Btu/h
85,300.0 95,536.0 114,302.0
Cooling kW
5.5 7.5 9.23
Power
Input
Heating kW
5.8 7.7 9.38
Cooling W/W
4.07
3.73 3.63
COP
Heating W/W
4.31
4.09 4.00
ECOP
Cooling &
Heating
W/W 6.8
6.5
Capacity Control
%
20
~
100 14
~
100 14
~
100
Type
-
Hermetically sealed scroll type
Compressor
NO.
-
2 2 3
Air Flow Rate
m
3
/min
190 232
Dimensions
(
H×W×D
)
mm
1670×930×770
1670×1340×770
Package
Dimensions
(
H×W×D
)
mm
1850×1010×850 1850×1420×850
Net Weight
kg
260 260 372
Gross Weight
kg
284 284 390
Sound Pressure Level
dB(A)
58 58 61
Type
-
R410A
Refrigerant
Charge kg
12.0 12.0 14.0
Refrigerant Oil
-
Refer to the nameplate of the compressor
Liquid mm
Φ
9.5
Φ
9.5
Φ
12.7
Suction
Gas
mm
Φ
22.2
Φ
22.2
Φ
28.6
Piping
Connections
Discharge
Gas
mm
Φ
19.1
Φ
19.1
Φ
19.1
Number of Max.
Connectable Indoor Unit
-
13 16 19
Ratio of the Connectable
Indoor Unit
-
50%
~
135
%
Recommended Power
Cord
mm
2
×NO.
6.0
×
5 6.0
×
5 10.0
×
5