Communication of the System
Ⅰ
. Communication system of GREE Heat Recovery D.C Inverter Multi-VRF includes:
1. Communication between the indoor unit and the outdoor unit;
2. Communication among the indoor units
3. Communication among the outdoor units( in modules combination)
4. Communication among pinboards of outdoor units( when increasing pinboards is needed.)
Ⅱ
.The communication way of GREE Heat Recovery D.C Inverter Multi-VRF includes:
1. All of the communication ways are
485 communication
2
Indoor units network: Dual-core twisted pair lines whose ends are three-pin XH plug are applied in the
communication between outdoor units-indoor units/ indoor units-indoor units.
3.
Outdoor units network: Dual-core twisted pair lines whose ends are four-pin XH plug applied in
communication between module to module.
Ⅲ
. Traits of communication for Heat Recovery D.C Inverter Multi-VRF
1. Communications among modules are by the mainboards connection inside modules
2. A communication pinboard is equipped in each module which can communicate with max, 16 indoor units
simultaneously.