13
Selection of Installation Location and Precautions
If choose the indoor unit with auxiliary electric heater which decides the capacity of circuit breaker. Below is
the circuit breaker models which should be specially configured.
Model of Indoor Units(with
auxiliary electric)
Capacity of Circuit Breaker
Min. Sectional Area of
Earth lead (mm
2
)
Min. Sectional Area of
Power Cord (mm
2
)
22
、
28
、
32
、
36 duct type units
10 1.0 1.0
40
、
45
、
50duct type units
13 1.5 1.5
56
、
63
、
71
、
80duct type units
20 2.5 2.5
90
、
100
、
112
、
125
、
140 duct
type units
13 1.5 1.5
28
、
36
、
45
、
50 cassette type
units
10 1.0 1.0
56
、
63
、
71 cassette type units
13 1.5 1.5
80
、
90
、
112
、
125 cassette type
units
13 1.5 1.5
22
、
25
、
28
、
32
、
36 ultra-thin
duct units
10 1.0 1.0
40
、
45
、
50 ultra-thin duct units
13 1.5 1.5
56
、
63
、
71 ultra-thin duct units
16 2.5 2.5
●
Noise Control
Install
☆
the unit
at a well-ventilated place; otherwise it might result in decreased working capacity or higher
noise.
Install
☆
the unit
securely on a base that can fully support its weight; otherwise vibration and noise might be
caused.
Install the outdoor unit so that the hot air or noise will not disturb your neighb
☆
ors.
Do not place any obstacle close the outlet of outdoor unit; otherwise it might result in decreased working
☆
capacity or higher noise.
If the air conditioner gives out abnormal noise during use, please immediately contact your dealer.
☆
●
Accessories for Installation Use
For the accessories for installation of indoor units and outdoor
units,
please see the Packing List in the
package.