Multi Variable Air Conditioners Indoor Unit for North America
66
P21
Corrected value settings of
environment temperature sensor
of IDU (for cooling, dehumidifying,
and air supply)
-15 to 15
P22
Corrected value settings of
environment temperature sensor
of IDU (for heating)
-15 to 15
P30
Static pressure settings for indoor
fan
Type 1: 03.04.05.06.07
Type 2: 01.02.03.04.05.06.07.08.09
P31
High-ceiling installation settings
00: standard-ceiling installation height
01: high-ceiling installation height
P32
Capacity adjustment function of
IDU
-40% to +40%
P34
Repeating validity for time-point
timing
00: invalid
01: valid
P35
Factory setting recovery for user
functions
00: invalid
01: factory setting recovery
P36
Factory setting recovery for
engineering settings
00: invalid
01: factory setting recovery
P40
Prevention for heat collection
00: disabled
10: 10 seconds
20: 20 seconds
30: 30 seconds
40: 40 seconds
50: 50 seconds
60: 60 seconds
P42
Project number settings of IDU
1-255
P43
Preferential operation settings
00: no preferential operation
01: preferential operation
P44
One-key project number setting
query for IDU
00: not displayed
01: displayed
P45
One-key project number reset for
IDU
00: invalid
01: project number reset
P46
Accumulated time clearing for air
filter cleaning
00: not cleared
01: cleared
P47
Prompt settings for air filter
cleaning
00: no cleaning prompt settings
10-39: The first digit indicates the pollution degree of the using
place and the second digit indicates the accumulated operating time
of IDU. The two digits are described as follows:
①
. Slight pollution: The first digit is "1". If the second digit is "0", it
indicates that the accumulated operating time is 5500 hours.
The accumulated operating time is added by 500 hours when
the second digit is increased by "1‖. When the second digit is
―9‖, the accumulated operating time is 10000 hours.
②
. Medium pollution: The first digit is "2". If the second digit is "0",
it indicates that the accumulated operating time is 1400 hours.
The accumulated operating time is added by 400 hours when
the second digit is increased by "1". When the second digit is
"9", the accumulated operating time is 5000 hours.
③
. Heavy pollution: The first digit is "3". If the second digit is "0", it
indicates that the accumulated operating time is 100 hours.
The accumulated operating time is added by 100 hours when
the second digit is increased by "1". When the second digit is
"9", the accumulated operating time is 1000 hours.
n0
System conservation operation
settings
00: comfortability preferred
01: conservation preferred
n1
Defrosting period settings
40: 40 minutes
50: 50 minutes
60: 60 minutes
n3
Forcible defrosting
00: no defrosting
01: forcible defrosting
Содержание GMV-N07G/A3A-D(U)
Страница 1: ...Multi Variable Air Conditioners Indoor Unit for North America Service Manual R410A R410A 60Hz GC201609...
Страница 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Страница 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Страница 37: ...Multi Variable Air Conditioners Indoor Unit for North America 31 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Страница 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Страница 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...