Multi Variable Air Conditioners Indoor Unit for North America
124
4. Disassemble the
centrifugal fan.
●Use a screwdriver to unscrew the
centrifugal fan.
5. Remove the
motor and
centrifugal fan.
●Use a screwdriver to unscrew the
centrifugal fan.
●Loosen the fasteners of the motor
and remove the motor from the
support.
●For motors that are accompanied
with supports, the supports need
removing as well.
6. Remove the
centrifugal fan.
●Use a hexagon to unscrew the fan
and remove the centrifugal fan from
the motor axle.
8. Install a new
motor.
●Assemble units based on the
reverse order of this procedure and
power on the units for test.
4.6 Two-way Cassette Type Indoor Uint
NOTICE! The following steps are specific for GMV-ND09TS/A-T(U) units. For other units, the
assembly and disassembly procedure is similar except the numbers of centrifugal fans and motors.
Removal of Fan Motor
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
1
.
Remove the grille
●Slip the fasteners on the panel,
open the grille, remove it
Содержание GMV-N07G/A3A-D(U)
Страница 1: ...Multi Variable Air Conditioners Indoor Unit for North America Service Manual R410A R410A 60Hz GC201609...
Страница 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Страница 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Страница 37: ...Multi Variable Air Conditioners Indoor Unit for North America 31 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Страница 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Страница 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...